Chapter 5: Technical specifications
112
2X Series Installation Manual
Communication port specifications
Ethernet
Ethernet 10/100BaseT port (10 Mbps)
Note:
For increased security, we recommend against using
Ethernet for remote connection to the control panel via the
Internet.
TCP/IP
IPv4
USB host port
USB 2.0, type A connector
USB device port
USB 2.0, type B connector
Fire network specifications
Maximum distance between
two control panels
1.2 km
Maximum capacity
32 loops and 32 nodes
Communication protocol
Proprietary protocol based on RS-485
Input and output specifications
Input and output overview
Configurable
outputs
General fire
outputs
General fault
outputs
24V AUX
output
Configurable
inputs
One-loop panel
2 Class B
1 Class A
2 (see note)
2 (see note)
1
2
Two-loop panel
4 Class B
2 Class A
2 (see note)
2 (see note)
1
2
Two-loop panel with
loop board
8 Class B
4 Class A
2
2
1
2
Repeater panel
0
2
2
1
2
Note: 1 supervised output and 1 potential-free relay.
Configurable inputs
Number of inputs
2 supervised inputs, end-of-line resistor 15 k
Ω, 1/4 W
Active value
60.2 Ω
≤
active value
≤
8 kΩ
Normal value
10 kΩ
≤
value
≤
20.2
kΩ
Short circuit values
≤
60.2 Ω
High-impedance fault value
8 kΩ < value < 10 kΩ
Open circuit values
≥
20.2 kΩ
Configurable options
See Table 46 on page 82
Содержание 2X Series
Страница 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Страница 6: ...iv 2X Series Installation Manual ...
Страница 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Страница 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Страница 121: ...Chapter 5 Technical specifications 2X Series Installation Manual 115 Figure 27 Large cabinet dimensions and views ...
Страница 122: ...Chapter 5 Technical specifications 116 2X Series Installation Manual Figure 28 Small cabinet dimensions and views ...
Страница 140: ......