Chapter 3: Configuration and commissioning
2X Series Installation Manual
43
3. Select Manual, and then select NO (to process mode change commands from
the day/night mode schedule and holiday calendar) or YES (to override mode
change commands from the day/night mode schedule and holiday calendar).
The default setting is NO (mode change commands from the Day/Night mode
schedule and Holiday calendar are processed as configured).
4. Select Mode, and then select DAY or NIGHT to define the default control
panel sensitivity mode if Manual (above) is set to YES.
The default setting is DAY. If Manual is set to NO, then no mode configuration
is required.
5. Select Disable delays in night mode, and then select which sounder, fire
routing, or fire protection delays to process or override when the control panel
is in night mode.
By default, all delays are disabled when the control panel is in night mode.
6. Press F4 (Enter), and then press F1 (Back).
7. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Notes on day and night mode settings
Day/night mode may be configured to change with a remote input. Depending on
the installation settings, the system may be configured to use an external input to
override the day/night mode setting until the following programmed change (if
any).
Control panels in the same network can have different day/night mode sensitivity
settings.
If the command filter is configured accordingly, a control panel can operate a
local day/night mode setting independently from other control panels in the same
network. A local day/night mode setting is indicated on the local control panel
LCD by the corresponding icon. See “Icons displayed on the LCD” on page 11.
If the control panel is a repeater, remember that the day/night mode displayed
corresponds to those control panels configured to accept the global sensitivity
mode command. Some control panels in the network may be operating with
locally-defined sensitivity settings.
The day/night mode setting for all control panels in a fire network is included in
the Firenet status report.
For more information on the global controls, see “Global controls” on page 57.
Содержание 2X Series
Страница 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Страница 6: ...iv 2X Series Installation Manual ...
Страница 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Страница 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Страница 121: ...Chapter 5 Technical specifications 2X Series Installation Manual 115 Figure 27 Large cabinet dimensions and views ...
Страница 122: ...Chapter 5 Technical specifications 116 2X Series Installation Manual Figure 28 Small cabinet dimensions and views ...
Страница 140: ......