Chapter 3: Configuration and commissioning
2X Series Installation Manual
71
3. Select Ethernet config.
4. Select Period, and then enter the value in seconds (1 to 99).
5. Select Fails, and then enter the value (1 to 10).
6. Press F4 (Enter), and then press F1 (Back).
7. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
CMS configuration
Select the CMS configuration option to configure central monitoring station
settings. Up to six monitoring stations can be added. Configuration options are
shown in the table below.
Table 32: CMS configuration options
Option
Description
Default value
IP/Port
Configures the CMS IP address and communication port.
000.000.000.000/
09999
Alarm
Configures the CMS priorities for reporting alarm events:
NO (no reporting), P (primary CMS), B1 (first backup CMS),
B2 (second backup CMS), etc. [1]
NO
Fault
Configures the CMS priorities for reporting fault events: NO
(no reporting), P (primary CMS), B1 (first backup CMS), B2
(second backup CMS), etc. [1]
NO
Cond
Configures the CMS priorities for reporting condition events:
NO (no reporting), P (primary CMS), B1 (first backup CMS),
B2 (second backup CMS), etc. [1]
NO
Enabled
Enables or disables communication with the CMS.
NO
Account
Configures the account information that identifies the
control panel. Maximum 6 digits (hexadecimal). Possible
values: 0 to 9 and A to F.
000000
Receiv.
Configures the four-digit TCP/IP receiver number for the
CMS.
0000
Line
Configures the four-digit TCP/IP line number for the CMS.
0000
Network
Configures the network type (Ethernet or GPRS).
ETH
FR_ERM [2]
Configures the event reporting mode for the corresponding
central monitoring station: Fire Routing mode (for alarm
event transmission) if checked or Event Reporting mode if
not checked.
Event Reporting
mode
[1] In the event of communication problems reporting an event to the primary CMS, the control
panel attempts to send the event notification to the configured backups in order of the assigned
priority.
[2] The global FR_ERM setting in General Configuration takes priority over any individual CMS
setting configured here.
Содержание 2X Series
Страница 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Страница 6: ...iv 2X Series Installation Manual ...
Страница 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Страница 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Страница 121: ...Chapter 5 Technical specifications 2X Series Installation Manual 115 Figure 27 Large cabinet dimensions and views ...
Страница 122: ...Chapter 5 Technical specifications 116 2X Series Installation Manual Figure 28 Small cabinet dimensions and views ...
Страница 140: ......