Chapter 3: Configuration and commissioning
68
2X Series Installation Manual
To update the firmware:
1. Select Panel setup from the Main menu, and then select Firmware update.
2. When prompted, open the control panel door and install a jumper onto JP4 on
the control panel PCB (see Figure 23 on page 68), and then press F3
(Reboot).
The control panel reboots. Follow the on-screen instructions.
3. When prompted, insert the USB flash drive with the firmware update into
either of the USB type A connectors, and then press F3 (Continue).
4. When prompted, remove the USB flash drive as described in “Removing a
USB device” on page 44.
Figure 23: USB and JP4 connectors on the control panel PCB
1. USB connectors
2. JP4
Printer configuration
Select the Printer configuration option to configure external or internal printers,
where available. Configuration options are shown in the table below. By default,
all printer configuration options are disabled.
Table 28: Printer configuration options
Option
Description
Used
Configures the printer status (used or not used)
RportMd [1]
Configures the external printer for report printing
NWEvent [2]
Configures the printing of system events for all control panels in the
network
Alarm [2]
Configures the printing of alarm events
Fault [2]
Configures the printing of fault events
Содержание 2X Series
Страница 1: ...2X Series Installation Manual P N 501 405003 1 31 REV 03 10 ISS 07NOV13 ...
Страница 6: ...iv 2X Series Installation Manual ...
Страница 20: ...Chapter 1 Introduction 14 2X Series Installation Manual ...
Страница 110: ...Chapter 3 Configuration and commissioning 104 2X Series Installation Manual ...
Страница 121: ...Chapter 5 Technical specifications 2X Series Installation Manual 115 Figure 27 Large cabinet dimensions and views ...
Страница 122: ...Chapter 5 Technical specifications 116 2X Series Installation Manual Figure 28 Small cabinet dimensions and views ...
Страница 140: ......