When there is no ignition (A01), check that the gas cock is
open and gas is available.
3.10
B
OILER
S
AFETY
S
YSTEMS
The boiler is protected from malfunctioning by means of internal
checks by the P.C.B., which brings the boiler to a stop if necessary.
In the event of the boiler being shut off in this manner, a code
appears on the display which refers to the type of shut-off and the
reason behind it.
There are two types of shut-off:
-
SAFETY SHUTDOWN:
for this group of errors (characterised
on the display by the letter “
E
E
”) the situation is automatically
removed as soon as the cause behind it is resolved.
As soon as the origin of the shutdown disappears, the boiler
starts up again and returns to its normal operation.
-
SHUTDOWN:
(characterised on the display by the letter “
A
A
”), is
not removed unless a manual intervention is made.
The boiler may return to operation only if reset, press the
button located at the centre of the display.
There follows a list of the shutdown modes and the respective codes
shown on the display.
Shutdown (“
A
A
” type): if such a situation occurs, it is necessary to
reset the boiler using the appropriate key. If this shutdown occurs
frequently, your local Service Agent should be contacted.
Safety shutdown: In the event that a safety shutdown occurs, it is
necessary to contact an Authorised Service Centre.
DISPLAY
CAUSE
A
A0
01
1
Too many attempts to ignite on start up
A
A0
02
2
No water or no water circulation in central
heating system
A
A0
03
3
The heating flow temperature exceeds 105°C
during operation
A
A0
07
7
Too many failures to ignite in one period
during operation
A
A3
33
3
Problem with the fan
A
A9
97
7
Problem with the electronic monitoring
A
A9
98
8
Problem with the electronic monitoring
A
A9
99
9
Problem with the electronic monitoring
DISPLAY
CAUSE
E
E 0
04
4
Domestic hot water temperature probe
in open circuit
E
E 0
05
5
Domestic hot water temperature probe
in short circuit
E
E 0
06
6
Heating flow temperature probe in open circuit
E
E 0
07
7
Heating flow temperature probe in short-circuit
E
E 0
08
8
Heating return temperature probe
in open circuit
E
E 0
09
9
Heating return temperature probe
in short-circuit
E
E 1
10
0
Under floor heating temperature probe
in open circuit
E
E 2
20
0
Flame detected with gas valve closed
E
E 3
30
0
Outdoor sensor open circuit
E
E 3
31
1
Outdoor sensor in short circuit
E
E 3
33
3
Fan operation sensed with no demand for
central heating or domestic hot water
E
E 3
34
4
Fan operation but air pressure switch
does not close
E
E 8
80
0
Remote Control CLIMA MANAGER room
sensor in open circuit or short circuit
E
E 9
94
4
Problem within the electronic system
E
E 9
95
5
Error reading flow or return temperature probe
E
E 9
99
9
Problem within the electronic system
DISPLAY
CAUSE
S
S0
01
1
Ignition failure on 1st attempt
S
S0
02
2
Ignition failure on 2nd attempt
Содержание ACO 27 MFFI
Страница 49: ...49 WIRING DIAGRAM FOR CONNECTION TO AN ARISTON UNVENTED CYLINDER DIAGRAM A ...
Страница 50: ...50 WIRING DIAGRAM FOR CONNECTION TO AN OPEN VENTED CYLINDER DIAGRAM B ...
Страница 57: ...57 FIG 7 19 FIG 7 20 FIG 7 21 FIG 7 22 FIG 7 23 FIG 7 24 O P FIG 7 18 ...
Страница 69: ...69 Model 27 32 RFFI SYSTEM ...
Страница 70: ...70 ...
Страница 71: ...71 ...
Страница 77: ...77 ...
Страница 78: ...78 11 BENCHMARK COMMISSIONING CHECKLIST ...
Страница 79: ...79 12 SERVICE INTERVAL RECORD ...