FITTING THE EXTERNAL SENSOR
The exter nal sensor is supplied with the interface PCB
(Fig. 2.33).
The external sensor should be sited no more than 50 m from the
boiler and on an external north facing wall, between 2 and 2.5
metres above the ground. It should also be ensured that the
external sensor is positioned out of direct sunlight.
To connect the external sensor, plug the interface PCB into
connector
CN6
on the main PCB (see Fig. 2.33).
To connect between the interface PCB and the external sensor,
it will be necessary to use 2x 0.5mm
2
cable, connected to the
two terminals on the external sensor and to Terminal B (Fig.
2.33) on the interface PCB.
Instructions on the activation and setting of the outdoor sensor
are detailed on pages 41 and 42.
Parameter P activates the external sensor, Parameter P6
modifies the thermal curve and Parameter P6 selects the
specific thermal curve for the type of system installed.
N
OTE
: W
HEN USING THE
ACO
BOILERS TO HEAT AN INDIRECT
CYLINDER
,
DO NOT USE THE EXTERNAL SENSOR AS THIS WILL
AFFECT THE RECOVERY TIME OF THE CYLINDER
.