8.6.4
Set DST Auto Stop Time
Command:
3,w,x,y,zDT
3,w,x,y,zDT sets the date and time when DST stops, where:
w =
Month (0, . . . , 11); 0 = Jan., 1 = Feb., . . . , 11 = Dec.
x =
WeekOfMonth (0, . . . , 5); 0 = First, 1 = Second,
2 = Third, 3 = Last, 4 = Second from Last, and 5 = Third from
Last.
y =
DayOfWeek (0, . . . , 6); 0 = Sun., 1 = Mon., . . . , 6 = Sat.
z =
Minutes after midnight z (0 through 1440).
Response:
C
8.6.5
Set Local Offset
Command:
mLT
mLT sets the local offset in 15-minute increments for
±
720 minutes
(
±
12 hours), where m equals the number of minutes, positive (East)
or negative (West). LT returns current setting.
Response:
C
8.6.6
Set Display Time Mode
Command:
mTD
mTD sets the display mode to either UTC (m = 0) or Local (m = 1) on
Model 1095C clocks only. TD returns current setting.
Response:
C
8.7
IRIG Data, IEEE P1344
Command:
m,n,oIR
m,n,oIR configures the control bits of the IRIG-B IEEE P1344 standard.
oIR returns setting, e.g. 0IR returns IRA:0 0 (means Channel A set to
IEEE Off and IRIG time set to UTC), where:
m = 0, IEEE P1344 control bits OFF; m = 1, control bits ON,
n = 0, IRIG Time = UTC; n = 1, IRIG Time = Local
o = 0, IRIG Output on Ch A; o = 1, IRIG Output on Ch B.
Response:
C