4.2.8
The Programmable Pulse B Screen
Select the Prog. Pulse B tab to configure how the Model 1095A/C sends
pulses to the Prog Pulse B terminals; it includes four modes and seven
pulse types. Prog. Pulse B is identical to Prog. Pulse A except that it
includes two additional modes: (1) Frequency, and (2) IRIG-B.
Figure 4.14: Programmable Pulse B Setup
Modes:
(1) Off, (2) Pulse, (3) Frequency, and (4) IRIG-B.
Pulse Mode Types:
(1) Pulse per Second, (2) Pulse per Minute, (3)
Pulse per Hour, (4) Pulse per Day, (5) Single Trigger, (6) Slow Code,
and (7) Seconds per Pulse.
Frequency:
Set frequency, from 1 to 1000, in pulses per second; no
other settings are available. Pulses have 50 percent duty cycle.
IRIG-B:
Select “IRIG-B" as Mode and go to IRIG tab, Channel B, to set
up IRIG-B preferences. IRIG-B from Channel B is independent from
IRIG-B from Channel A.
Polarity, Alarm Time Mark, Pulse Width, and Pulse Delay:
See
definitions on Programmable Pulse A in Section 4.2.7.
36