56
Timing, IRIG-B and Pulses
For important considerations about IRIG-B connections, distribution of signals and accuracy, down-
load the file,
IRIG-B accuracy and connection requirements.pdf at the following link:
http://arbiter.com/resources/documentation.php
and select
Timing and Frequency
, then select
Ap-
plication Notes/Option Information
.
7.4.3
Synchronizing Multiple IED’s From One Masterclock Output
In many installations, master clock signals are “fanned out” to a number of devices. This method
makes more efficient use of the clock synchronizing capability since the clock drivers are designed
to handle multiple loads. The exact number of possible loads must be determined from the input
impedance of each connected IED. For example, if the input impedance of the IED is 5 kilohms,
determine the device current (I) as follows:
(7.1)
I
=
V
÷
R
dev
= 5
V olts
÷
5000
Ohms
= 0
.
001
Amps
(1
mA
)
If you were to connect ten of the same IED’s to the same output, then the total current drawn
would be 10 x 0.001 A = 0.01 A (10 mA).
7.4.4
Connecting Unmodulated IRIG-B
To drive multiple loads from one unmodulated IRIG-B output, make sure that the loads are wired
in parallel. Some technicians might call this “daisy-chaining”, however the idea is to drive all of
these loads in parallel from the single output. It is much simpler to connect loads to unmodulated
IRIG-B than for modulated, because all of the loads are driven at the same voltage.
To determine load current for one Unmodulated IRIG-B output:
1. determine the number of loads to be connected to a single clock output
2. determine the impedance (or resistance) of each load
3. calculate the load current for each device (
I
dev
= 5
V
÷
R
dev
)
4. sum up all the load currents for the total current for one clock output.
Another method is to determine the lumped impedance of all of the connected IED’s in parallel.
Then, determine the overall current by dividing the drive voltage (5 V) by the computed lumped
impedance value. This current should not exceed 75 mA.
7.4.5
Connecting Modulated IRIG-B
The total load capacity for the modulated IRIG-B driver depends on the type and number of loads.
The main difference in computing the load capacity for modulated IRIG-B and unmodulated IRIG-
B is that most of the modulated IRIG-B decoders are fairly sensitive to the peak-to-peak voltage.
When adding loads, the clock’s modulated driver produces more current, which is passes through
the internal source resister, dropping the available output voltage. The open circuit voltage (i.e.
with no loads) is approximately 4.5 Vpp, so any connected loads will cause the available voltage to
drop. It is a simple task to compute the available output voltage (Vpp) with a known current.
(7.2)
V pp
= 4
.
5
V pp
−
I
×
19
.
6
Ohms
Содержание 1084A
Страница 4: ...iv ...
Страница 6: ...vi ...
Страница 18: ...xviii LIST OF FIGURES ...
Страница 23: ...1 4 Attaching Rack Mount Ears to 1084A B C Series Clocks 3 Figure 1 2 Attaching Rack Mount Ears ...
Страница 24: ...4 Unpacking the Clock ...
Страница 36: ...16 Connecting Inlet Power Input and Output Signals ...
Страница 39: ...4 1 GPS Antenna Installation 19 Figure 4 2 Antenna Mounting Bracket Figure 4 3 Antenna Mounting with AS0044600 ...
Страница 44: ...24 GPS Antenna and Cable Information ...
Страница 114: ...94 Startup and Basic Operation ...
Страница 123: ...B 4 Physical Dimensions 103 Figure B 1 Suggested Mounting of the AS0094500 Surge Arrester ...
Страница 124: ...104 Using Surge Arresters ...
Страница 134: ...114 Options List C 6 2 Option 06 Firmware Setup Figure C 3 Option 06 Firmware Setup ...
Страница 142: ...122 Options List Figure C 5 Option 06 Output Jumper Settings ...
Страница 143: ...C 6 Option 06 Parallel BCD Output 1 millisecond Resolution 123 Figure C 6 Option 06 Board Layout and Jumper Locations ...
Страница 157: ...C 10 Option 17 Parallel BCD Output and Second RS 232C Port 137 Figure C 12 Option 17 Output Jumper Settings ...
Страница 158: ...138 Options List Figure C 13 Option 17 Board Layout and Jumper Locations ...
Страница 163: ...C 13 Option 20A Four Fiber Optic Outputs 143 Figure C 14 Option 20A Jumper Locations ...
Страница 170: ...150 Options List Figure C 16 Option 23 Internal Jumper Setup ...
Страница 172: ...152 Options List Figure C 17 Option 27 Jumper Locations ...
Страница 190: ...170 Options List Figure C 20 Option 29 Connector Signal Locations ...
Страница 246: ...226 Options List ...