- 14 -
✻
✻
✻
✻
81 ZONE LISTS
Use this mode to define zone lists for Powerline Carrier Devices and/or for the chime by zone feature. Press
✻
81
while in programming mode.
Notes:
(1) Entering a number other than one specified will give unpredictable results.
(2) Do not assign zones with zone types 20, 21 or 22 to a zone list.
8 I
ZONE LIST PROGRAMMING
0 = Exit mode, upon which this prompt blinks.
1 = Enter mode
A 0 I
ZONE LIST NUMBER
Enter the 2-digit zone list number (01-03) to be programmed (use zone list 03 for chime by zone feature).
[
✻
] = Continue
00 = Exit mode (displays blinking 81; enter
✻
+ desired data field or menu mode number)
b
zz
ZONE ENTRY TO LIST
Enter the 2-digit zone number (
zz
) to be added to this zone list. The system will announce the Voice
Descriptor for the selected zone, if it is programmed.
[
✻
] = Accept zone number and enter the next zone number
00 = Accept zone number and continue to next prompt
C
DELETE ENTIRE ZONE LIST?
0 = Don’t delete; continue to next prompt
1 = Delete the current zone list
d
DELETE SPECIFIC ZONES FROM LIST?
0 = Don’t delete; continue to next zone list number (prompt A 01)
1 = Continue to delete zones prompt
E
DELETE ZONES
Enter the 2-digit zone number to be deleted from the current zone list. When deleting a zone(s) from the
zone list, if the selected zone has a Voice Descriptor programmed, upon deletion it will be announced as
a confirmation that it has been deleted.
[
✻
] = Delete zone and enter next zone to be deleted
00 = Return to next zone list number (prompt A 01)