POWERLINE CARRIER DEVICES WORKSHEET FOR
✻
✻
✻
✻
80, and
✻
✻
✻
✻
81.
Applicable only if Powerline Carrier Devices are to be used, or chime-by-zone feature is used.
UL
Powerline Carrier Devices have not been evaluated by UL.
✱
80
OUTPUT DEVICES
Fill in the required data on the worksheet on below and follow the programming procedure in the Installation
Instructions as you enter the data during the displays and prompts that appear in sequence.
Note
:
Field
✱
25 must be programmed with a House Code.
S T A R T
either or both
S T O P
either or both
DEVICE
NUMBER
ACTION
(aa)
EVENT
ZONE
TYPE
(et)
LIST
(zl)
ZONE TYPE
SYS OPERATION (zt)
RESTORE
ZONE LIST (zl)
ZONE TYPE/
SYS OPERATION (zt)
P.L.C.D.*†
01
P.L.C.D.*†
02
P.L.C.D.*
† 03
P.L.C.D.*
04
P.L.C.D.* †
05
P.L.C.D.*†
06
SYS. P.L.C.D.*†
07
SYS. P.L.C.D.*†
08
[2]
[33]
[36]
E-mail Event Trigger
09
E-mail Event Trigger
10
E-mail Event Trigger
11
E-mail Event Trigger
12
E-mail Event Trigger
13
E-mail Event Trigger
14
E-mail Event Trigger
15
E-mail Event Trigger
16
[2]
[33]
[36]
* P.L.C.D. = Powerline Carrier Device (X10).
Where:
A = DEVICE ACTION
0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off.
ET = EVENT TYPE
0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble.
Z L = ZONE LIST
1, 2, or 3 (from Field
✱
81) or 0 = Not Used.
"START" ZONE LIST: Upon alarm, fault, or trouble of ANY zone on this list, device action will START.
"STOP"
RESTORE
of
ZONE LIST: Upon restore of ALL zones on this list, device action will STOP.
It need not be same list as used for START.
Note:
Do not assign zones with types 20, 21, or 22 to a zone list.
3
ZT = ZONE TYPE/
SYSTEM OPERATION
Choices for Zone Types are:
00 = Not Used
07 = 24 Hour Audible
01 = Entry/Exit#1
08 = 24 Hour Aux
02 = Entry/Exit#2
09 = Fire Zone without Verification
03 = Perimeter
10 = Interior with Delay
04 = Interior Follower
14 = Carbon Monoxide
05 = Trouble Day/Alarm Night
24= Silent Burglary
06 = 24 Hour Silent
Choices for System Operation are:
20 = Arming–Stay
33 = Any Alarm*
42 = System Battery Low
21 = Arming–Away
36 = At Bell Timeout**
43 = Communication Failure
22 = Disarming (Code + OFF)
38 = Chime
52 = Kissoff
31 = End of Exit Time
39 = Any Fire Alarm
58 = Duress
32 = Start of Entry Time
40 = Bypassing
* Except ZT=08, 09, 14 or 16.
** Or at Disarming, whichever occurs earlier.
Note:
In normal operation mode:
For Devices 1-6:
For Devices 7 and 8:
N = device (unit) number
Fu Lights On + N
Code + Fu 4 + N
(Entry
starts
Device N)
Fu Lights Off + N
Code + Fu 7 + N
(Entry
stops
Device N)
Note
:
Any
zone in "ZT" going into alarm, fault, or trouble will activate device with the
exception of 01, 02 when the system is in alarm.
Any
zone that restores will
stop device action.