12
TC5-1V10SA rev.06
TC5-1V10SA
3
Defective Probes
If a defective probe is detected, the Defective Probe Pilot Light turns on. The
room temperature shown on the display is then the average temperature
measured by the probes in working condition. The controller will operate
according to this temperature.
To identify the defective probe:
n
Set the selection knob to
ROOM
TEMPERATURE
. The room tem-
perature is displayed.
n
Press the push-button. If the
probe connected to input # 1 and
supplied with the controller is not
defective, the letters"
PR1
" are dis-
played, alternating with the on/off
state of the probe and the tem-
perature measured by the probe.
If the probe is defective, the let-
ters "
PR1
" are displayed, alternat-
ing with the state of the probe and
the letter "
P
".
For each additional probe connected to the controller:
n
Press the push-button once again. If the probe is not defective, the
letters "
PR#
" (where # is the number of the input to which the probe is
connected) are displayed, alternating with the on/off state of the probe
and the temperature measured by the probe. If the probe is defective,
the letters "
PR#
" are displayed, alternating with the on/off state of the
probe and the letter "
P
".