47
TC5-1V10SA rev.06
ALARM SETTINGS
The controller sets off an alarm in the case of a power failure, a fault in the
supply circuit or a high or low temperature. Temperature alarms are de-
fined according to the set point as shown in the diagram below.
Adjusting the Alarm Settings
The high and low alarm offsets range from 0.5
o
F to 40
o
F.
n
Set the selection knob to
ALARM
— LOW / HIGH OFFSET
. The
current low alarm offset flashes on
the display, alternating with the
word "
LO
".
n
Use the adjustment knob to set the
low alarm offset to the desired
value.
n
Press the push-button. The current high alarm offset flashes on the
display, alternating with the word "
HI
".
n
Use the adjustment knob to set the high alarm offset to the desired
value.
Room
Temperature
Set Point
High Alarm Offset
Time
High Temperature Alarm
Low Alarm Offset