41
TC5-1V10SA rev.06
TC5-1V10SA
3
Adjusting Mist Timer Settings
Time on and time off can be adjusted between 0 and 60 minutes, in increments
of 1 minute. To deactivate mist cooling, set time on to zero.
n
Set the parameter selection knob to
MIST — TIMER/OFFSET
.
The current time on for the mist cycle is displayed, alternating
with the letters "
On
".
n
Use the adjustment knob to set time on to the desired value (in min-
utes).
n
Press the push-button. The current time off for the mist cycle is dis-
played, alternating with the letters "
Off
".
n
Use the adjustment knob to set time off to the desired value (in min-
utes).
4
Adjusting Humidity Turn Off Level
The humidity turn off level is the humidity level at which mist units are turned
off. This parameter is not displayed unless humidity compensation is
activated (see Humidity Compensation). The value ranges from 0 to 100%.
When the mist units are turned off, the compensation pilot light turns on.
n
Set the parameter selection knob to
MIST — TIMER/OFFSET
.
The current time on for the mist cycle is displayed, alternating
with the letters "
On
".
n
Press the push-button four times. The current turn off level flashes on
the display.
n
Use the adjustment knob to set the turn off level to the desired value.