32
TC5-1V10SA rev.06
TC5-1V10SA
Interaction Between Temperature and Minimum Speed
Curves
•
The minimum speed curve can be activated only if the tempera-
ture curve is already activated
•
All points of the minimum speed curve other than the first one are
automatically given day numbers identical to those specified for the tem-
perature curve. Only the first point of the minimum speed curve has an
adjustable day number. This day number must be greater or equal to the
day number specified for the first point of the temperature curve and less
than the day number specified for the second point of the temperature
curve (see example 1).
TEMPERATURE CURVE
POINT
1
POINT
2
MINIMUM SPEED CURVE
d5
d20
d5 to d19 (adjustable)
d20 (not ajustable)
EXAMPLE 1
Table 1.
''Set Point - 5.0°F (2.8°C) - Heater Offset - Stage 11 Differential''
OR
''Set Point'', if the parameter settings are such that the pre-
ceding value is greater than the set point.
STAGE 11
OPERATION
THRESHOLD VALUE
Cooling
''Set Point - 5.0°F (2.8°C)''
Heating
Содержание TC5-1V10SA
Страница 1: ...TC5 1V10SA EnvironmentControl USER SMANUAL M 890 00167 rev 06 REV 01...
Страница 6: ...6 TC5 1V10SA rev 06 LOCATION OF THE CONTROLS...
Страница 59: ...NOTES NOTES...