Engineer
42
MAXXfl o EVO
PARAMETER DESCRIPTION
FACTORY
DEFAULT
NOTES
Modbus
6651
Modbus slave address
---
Defi ne Modbus settings
6652
Modbus laud rate
19,200
Defi ne Modbus settings
6653
Modbus parity
Even
Defi ne Modbus settings
6654
Modbus stop bit
1
Defi ne Modbus settings
Error / Fault
6700 - 6999
Fault history
---
Fault history for last 20 reported faults. Time, date , phase no,
error codes and sub codes
Service/special operation
7040
Burner hours run mainte-
nance interval
---
Burner run hours that must be exceeded before a mainte-
nance message is displayed
7041
Burner hours run since
maintenance
---
COUNTER CAN BE RESET
Burner run hours elapsed since
maintenance was carried out and the counter was reset
7042
Burner starts maintenance
interval
---
Number of burner starts that must be exceeded before a main-
tenance message is displayed
7043
Burner starts since main-
tenance
---
COUNTER CAN BE RESET
Number of burner starts since
maintenance was carried out and the counter was reset
7044
Maintenance interval
12 months
Limit of time elapsed before a maintenance message is dis-
played
7045
Time since maintenance
---
COUNTER CAN BE RESET
Number of months elapsed since
maintenance was carried out and the counter was reset
7130
Chimney sweep function
Off
Function used to operate the individual burner at either mini-
mum or maximum gas rate. Function useful when performing
a fl ue gas analysis. NB The maximum fl ow temperature per-
mitted is 78
O
C, if the fl ow temperature exceeds this value the
function will be turned off . Open hot water outlets if necessary
to ensure that the maximum fl ow temperature is not exceeded.
7131
Chimney sweep function
burner output
High fi re
Sets burner output level in chimney sweep mode
7143
Controller stop function
Off
Function used to operate the individual burner at a rate from
0% to 100% modulation levels. It is also possible to view the
performance of the ionisation current. NB The maximum fl ow
temperature permitted is 78
O
C, if the fl ow temperature ex-
ceeds this value the function will be turned off . Open hot water
outlets if necessary to ensure that the maximum fl ow tempera-
ture is not exceeded
7145
Controller stop setpoint
100%
Defi nes the burner modulation rate for the function
7170
Telephone customer
service
---
A customer service number can be entered into this line,
which will be displayed on the GUI when there is a fault or
when the maintenance symbol is displayed.
7250
PStick storage pos
---
Defi nes the parameter set selection from a manufacturers
programming stick, for purposes of fi rmware updates.
7251
PStick data description
---
Display line for contents of inserted manufacturers program-
ming stick.
7252
PStick command
---
Defi ne the operation of the inserted manufacturers program-
ming stick (e.g. read from stick).
7254
PStick progress
---
Display line for programming stick reading/writing progress in
%