3.5 CONSUMER
This function displays information about the live operational status of the items external to the operation of
the water heater.
Example screen:
Useful parameters viewable:
PARAMETER
DESCRIPTION
NOTES
8003
State DHW
Current status of DHW water
8830
DHW temp
Current temperature of DHW water
8831
DHW temp set point
DHW set point
8835
DHW circulating temp
Temperature of water returning to the DHW tank from the
secondary return system
8836
DHW charging temp
Temperature of the heated water entering the DHW tank
8950
Segment fl ow temp actual
Temperature of the heated water entering the DHW tank
8951
Segment fl ow temp setpoint
Setpoint of heated water entering the DHW tank
9009
Water pressure H3
Current primary system pressure
9016
Special temp 1
DHW tank Temperature of the fi rst optional BUFFER
SS300-10
9017
Special temp 2
DHW tank temperature of the second optional BUFFER
SS300-10
9031 - 9034
State multifunctional relays
State of relay operations on control PCB
9050 - 9058
State Multifunctional relays
(module 1)
State of relay operations on optional AGU2.5 extension
module