Engineer
41
MAXXfl o EVO
4.5 COMPLETE PARAMETER LIST TABLE (CONTINUED)
PARAMETER DESCRIPTION
FACTORY
DEFAULT
NOTES
Confi guration (continued)
6032
Relay output QX23
module 1
None
Defi nes the purpose of the output QX23 on a AGU2.550 clip-
in extension module
6040
Sensor input BX21
module 1
None
Defi nes the purpose of the sensor input BX21 on a AGU2.550
clip-in extension module
6041
Sensor input BX22
module 1
None
Defi nes the purpose of the sensor input BX21 on a AGU2.550
clip-in extension module
6046
Function input H2
module 1
None
Defi nes purpose of H2 multi-use input on a AGU2.550 clip-in
extension module
6047
Contact type H2
module 1
Normally Closed
NC
Defi ne whether the input is NO or NC (for 0 - 10 Volt setup
this value is ignored)
6049
Voltage value 1 H2
module 1
0
Defi ne a voltage value 1 that applies to function value 1 (e.g.
0.5V)
6050
Funct value 1 H2
module 1
0
Defi ne a function value 1 that applies to voltage value 1
(e.g. 400 for 40.0
O
C)
6051
Voltage value 2 H2
module 1
0
Defi ne a voltage value 2 that applies to function value 2
(e.g. 10.0V)
6052
Funct value 2 H2
module 1
0
Defi ne a function value 2 that applies to voltage value 2
(e.g. 700 for 70.0
O
C)
6200
Store sensor
Used to store the current sensors available to the controls at
the present time. Useful in clearing errors that may be caused
by sensor removal, as the controls will continue to give error
messages for a sensor that has been removed. (NB. When
sensors have been stored to remove a sensor fault , It may be
necessary for midnight to pass on the internal clock before a
sensor missing fault code is cleared completely).
6220
Device SW version
-
Version of Software in use
6230
Info 1 OEM
-
Year of software in use
6231
Info 2 OEM
-
Code for software in use
6258
info 3 OEM
-
Not currently used
6259
Info 4 OEM
-
Not currently used
LPB System
6600
Device address
1 or 2
On a single Heat Engine MAXXfl o EVO (30 & 60 models) the
device address = 1. For twin Heat Engine MAXXfl o EVO (90 &
120 models) the Top HE address = 1 and the bottom HE = 2
6601
Segment address
0
Used when more than one MAXXfl o EVO heater is connected
to an OZW672.04 or OZW672.16 Web Server. Each heater
must have a unique segment number (Max 16) for each
MAXXfl o EVO to be separately identifi able.
6605
LPB Power supply status
-
Status of power supply for OCI345 units (90 & 120kW models
only)
6612
Alarm delay
2 mins
This is the delay that is built into the controls to avoid report-
ing short term/temporary faults. When a fault in the controller
is fi rst present there will be a delay of this parameter value
before the fault relay is activated. If short term faults are unde-
sirable increase this value to eliminate them.
6640
Clock time source
Controller is
the time clock
master
If the MAXXfl o EVO is connected to an OZW672 Web server,
the Web server will be the time “clock master”. If this is the
case this parameter would need to be change to “slave with
remote setting”, as it is not possible to have two “Time clock
masters” connected on the same communications bus.