4.5 COMPLETE PARAMETER LIST TABLE
PARAMETER DESCRIPTION
FACTORY
DEFAULT
NOTES
Time of day and date
1
Time & Date
-
Current time and date settings. These settings can be
changed.
5
Start of summertime
-
Date of start for British Summer Time. An automatic one
hour adjustment will be made at 01:00 on this date. Please
remember that this date changes by a few days every year, so
adjustment of these dates at the start of the year is recom-
mended.
6
End of summertime
-
Date of start for British Winter Time. An automatic one hour
adjustment will be made at 01:00 on this date. Please re-
member that this date changes by a few days every year, so
adjustment of these dates at the start of the year is recom-
mended.
Operator section
20
Language
English
Change languages if required
40
Used as
Operator unit 1
Operator unit 1 only should be set
42
Assignment device 1
-
Has no eff ect on DHW operation
44
Operation zone 2
-
Has no eff ect on DHW operation
46
Operation zone 3
-
Has no eff ect on DHW operation
48
Warmer / cooler device 1
-
Has no eff ect on DHW operation
70
Software version
-
Current fi rmware version for this Graphical User Interface
(GUI)
Time program 4 (water heater)
Set time program
Optimised for
BS EN 13302-1
Used to set the time program for DHW heating (can also be
set on the DHW water heater menu of the user screen) Follow
section 2.3 for instruction on how to set the time clock.
576
Default values
06:00 - 22:00
daily
Reverts time clock settings to default values
Time program 5 (Q4 secondary return pump)
Set time program
24 hours every
day
Used to set the time program for DHW secondary return. Fol-
low section 2.3 for instruction on how to set the time clock.
616
Default values
06:00 - 22:00
daily
Reverts time clock settings to default values
DHW
1600
DHW operating mode
-
On or Standby (operation via switch on front of heater)
1610
Nominal setpoint
60
O
C
Normal DHW set point (setpoint when activated within pro-
gram 4 times)
1612
Reduced setpoint
15
O
C
Optimised for
EN13302-1
This reduced temperature setpoint is active when the current
time is outside the water heating time program settings (time
program 4).
1610
1612
Max setting
Example: