Page 2
FIREFINDER SERIES II
INSTALLATION,
COMMISSIONING
&
OPERATION
2
System Overview
The
FireFinder
Series II
is an Intelligent Analogue / Addressable and / or Conventional Fire Alarm
Control Panel capable of supporting:
Apollo Discovery and XP95 Intelligent Detectors, Multisensor, Photoelectric, Ionisation,
Thermal (heat) and CO detectors.
Addressable Initiating Devices: Modules that monitor any conventional normally open
contact such as supervisory switches and flow switches.
Conventional two wire zone detector circuits
Multiple input/outputs
High Level Interfaces
SmartGraphics
SmartTerminal
Remote LED mimics
Peer to Peer networking
Master Slave (Main - Sub) networking
Main panel plus Data Gathering Panels networking
The panel is built to comply with the following standard:
Australian Standard: AS 4428 parts 1 & 5
E.O.L
3K3
CONVENTIONAL ZONE
USING CONVENTIONAL DETECTORS
AND BASES
CONVENTIONAL ZONE
CIRCUIT
ADDRESSABLE
LOOP
ISOLATOR
ION
OPTICAL
HEAT
ANALOGUE DETECTORS
MANUAL CALL
POINT ( MCP )
ISOLATOR
E.O.L
6K2
4K7
4
K
7
F I R E
ALARM
PRESS HERE
TO BREAK
F I R E
ALARM
PRESS HERE
TO BREAK
HIGH LEVEL
INTERFACE /
EV3000
AS PER INPUT 1
AS PER INPUT 1
20K
EOL
4K7
N/O INPUT
SWITCH
RELAY
O/P 1
IN-1
IN-2
IN-3
C1
NC
NO
C2
NC
NO
C3
NC
NO
RELAY
O/P 2
RELAY
O/P 3
FIREFINDER FACP
SINGLE INPUT
DEVICE
FLOW SWITCH
E.O.L 20K
LOOP SOUNDER
L1
L2
E.O.L 10K
SOUNDER
SOUNDER
CONTROL
+
-
+24V DC
N/O
C
N/C
RELAY
OUTPUT
AUX OUTPUTS
INPUT/OUTPUT
UNIT
CONVENTIONAL DETECTORS
MAXIMUM OF 20
ZONE MONITOR
OUT
IN
SPECIFICATIONS:
MAX LENGTH = 2KM
MAX RESISTANCE = 50ohms
MIN CABLE SIZE = 1.5mm²
MONITORED
INPUT
+
-
+24V DC
THREE INPUT / OUTPUT
DEVICE
E
.O
.L
2
0
K
ANCILLARY
SERVICES
Figure 1: Typical Application