Page 34
FIREFINDER SERIES II
INSTALLATION,
COMMISSIONING
&
OPERATION
8.8
Function Programming
Press
To display the Level III Programming Menu.
ON SITE PROGRAMMING MENU
0: CONV ZONE 1: DEVICE 2: INPUT 3: OUTPUT
4: PANEL BASED MCP 5: SUB ADDRESS 6: WDOG
SELECT NO.
Figure 43: Programming Menu
8.8.1 Conventional Zone Programming
Press
Zone:
Key in the zone number and enter or change the description (
DESC
) by pressing
buttons to move the flashing underline or curser. The numeric buttons multiple times to access
characters while at the same time using
EDIT Zx DESC AND TYPE SETTING
DESC < ZONE >
TYPE <
ALPHA KEYS ARE ACTIVE
Figure 44: Zone Description & Type Programming
EDIT Z CONFIGURATION
CONFIG LATCHING
use < or > to change alarm setting
Figure 45: Brigade Options
Press
to move to the
TYPE
field or edit the information.
Press
to move between fields use the reciprocal button
By going through all the fields a second screen can also be accessed to show the Output options.
Press
to step through these fields.
The keys
are used to set the Y/N field, that is the selected Zone that will activate the
Brigade Options ALRM, BELL etc and Config.
EDIT Z I/O GROUPS
GROUP 1: GROUP 2: GROUP 3:
GROUP 4: GROUP 5: GROUP 6:
Enter GROUP NO:
Figure 46: Zone Configuration Latching / Unlatching
Use
or
to change the setting
Configuration settings are Latching, Non-Latching, AVF, Self Reset (0 to 99 seconds). After setting
the Configuration the ZONE I/O GROUPS are programmed.
ENTER Zx BRIGADE OPTIONS AND CONFIG
ALRM: Y/N BELL: Y/N AUX: Y/N SPK: Y/N AIF: Y/N
ALARM LED: Y/N CONFIG: LATCHING
use < or > to change setting
Figure 47: Zone I/O Groups