15: Inverter Voltage Adjustment
Interface
Setting
After it shows
“15” in parameter 1, please press
“Enter” key first. Then, you may choose
Ad
or
SU
to
adjust inverter voltage in
Parameter 1
by pressing
“Up” or “Down” key. After pressing “Enter” key to
confirm your selection, it will jump to parameter 2 to set
up the value.
Parameter 2:
the voltage range is from 0V to 6.4V, the
default value is 0V.
16: Output Voltage Calibration
Interface
Setting
After it shows “16” in parameter 1, please press “Enter”
key first. Then, you may choose
Ad
or
SU
to adjust output
voltage in
Parameter 1
by pressing “Up” or “Down” key.
After pressing “Enter” key to confirm your selection, it will
jump to parameter 2 to set up the value.
Parameter 2:
the voltage range is from 0V to 6.4V, the
default value is 0V.
17: Charging Current Setting
Interface
Setting
After it shows “17” in parameter 1 and “Cur” in parameter 2,
please press “Enter” key first. Then, you may select 01, 02, 03
or 04 to set the charging current from 1A to 4A in
Parameter 1
.
Then, calibrate the charging current by selecting “+” or
“-“ in
Parameter 2
.
± 0~± 5:
You may choose ‘+’ as
Add
or ‘-’ as
Sub
to adjust
charging current. This setting number is the first number after the
decimal point.
For example, if setting value is “+” and “3”, it means the
calibrated formula is to add 0.3A. The setting charging current
will become 4.3A as shown in left screen. (4A +
0.3A = 4.3A.)