15
User Manual
_________________________________________________________
© 2020 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com
All SurgeX Hardwired Security Plus UPS system
’s
OUTPUT must be
protected by proper sized AC disconnect device. The recommended
disconnect device ratings at full rated load are listed below:
2.0 kVA, Input 120V, Output 100-120V
20 AMP
2.0 kVA, Input 208-240V, Output 200-240V
10 AMP
3.0 kVA, Input 120V, Output 100-120V
30 AMP
3.0 kVA, Input 208-240V, Output 200-240V
15 AMP
4.0 kVA, Input 208-240V, Output 120-240V
20 AMP
5.0 kVA, Input 208-240V, Output 120-240V
25 AMP
6.0 kVA, Input 208-240V, Output 120-240V
30 AMP
8.0 kVA, Input 208-240V, Output 120-240V
50 AMP
10.0 kVA, Input 208-240V, Output 120-240V
65 AMP