13: Battery Voltage Adjustment
Interface
Setting
After it shows
“13” in parameter 1, please press
“Enter” key first. Then, you may choose
Add
or
SUB
to adjust battery voltage in
Parameter 1
by pressing
“Up” or “Down” key. After pressing “Enter” key to
confirm your selection, it will jump to parameter 2 to set
up the value.
Parameter 2:
the voltage range is from 0V to 5.7V, the
default value is 0V.
14: Charger Voltage Adjustment
Interface
Setting
After it shows
“14” in parameter 1, please press “Enter”
key first. Then, you may choose
Ad
or
SU
to adjust charger
voltage in
Parameter 1
by pressing
“Up” or “Down” key. After
pressing
“Enter” key to confirm your selection, it will jump to
parameter 2 to set up the value.
Parameter 2:
the voltage range is from 0V to 9.9V, the
default value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
*We strongly suggest using the default value (0). Any
modification should be suitable to battery