05: ECO Mode Enable/Disable
Interface
Setting
Parameter 2:
Enable or disable ECO function. You may
choose following two options:
DIS:
disable ECO function
ENA:
enable ECO function
If ECO function is disabled, voltage range and fre-
quency range for ECO mode still can be set, but it is
meaningless unless the ECO function is enabled.
06: Voltage Range for ECO Mode
Interface
Setting
Parameter 1 & 2:
Setting acceptable voltage range for
ECO mode. Set up the range by setting high and low
points. When it shows
“LLS” in parameter 2, please
press
“Enter” key and it will show “LS” in parameter
1. Now the low point in parameter 2 can be set up by
pressing
“Up” or “Down” key.
LS:
Low voltage point in ECO mode. The setting range
is from 5% to 10% of the nominal voltage.
Pressing
“Enter” key to confirm the setting value for low
point. Then, it will show HS in parameter 1. Set up high
point in parameter 2 by pressing
“Up” or “Down” key.
HS:
High voltage point in ECO mode. The setting range
is from 5% to 10% of the nominal voltage.