3) 120V Outputs
Output wiring
– 120V
NOTE 1:
SSO Tap Selection needs to be set to match the input
voltage. Install a jumper between 0-208V or 0-240V.
NOTE 2:
There are 2 sets of 120V outputs. Each set can carry half
of the total UPS capacity.
NOTE 3:
Make sure that the wires are connected tightly to the
terminals.
NOTE 4:
Install the output breaker between the output terminal and
the load. The breaker should be qualified with
leakage current protection if necessary.