09: Battery Backup Time Setting
Interface
Setting
Parameter 2:
000~999:
Set the maximum backup time from 0min
to 999min. UPS will shut down to protect battery after
backup time arrives. The default value is 990min.
DIS:
Disable battery discharge protection and backup time will
depend on battery capacity.
The default value is DIS.
10: Reserved
Interface
Setting
Reserved
11: Reserved
Interface
Setting
Reserved
12: Hot Standby Function Enable/disable
Interface
Setting
Parameter 2: HS.H
Enable or disable Hot standby function. You may
choose following two options in
Parameter 2:
YES:
Hot standby function is enabled. It means that the
current UPS is set to host of the hot standby function,
and it will restart after AC recovery even without
battery connected.
NO:
Hot standby function is disabled. The UPS is
running at normal mode and
can’t restart without
battery.