User Manual
_________________________________________________________
© 2020 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com
2) 120V and 240V Output
Output wiring
– 240V & 120V
NOTE 1:
SSO Tap Selection needs to be set to match the input
voltage. Install a jumper between 0-208V or 0-240V.
NOTE 2:
Split phase wiring, load shall be balanced 50 / 50 on each
side of transformer taps.
NOTE 3:
Make sure that the wires are connected tightly to the
terminals.
NOTE 4:
Install the output breaker between the output terminal and
the load. The breaker should be qualified with
leakage current protection if necessary.