background image

10

 

 

                                                                                                                          

                                                                                                                      

User Manual 

        _________________________________________________________ 

           © 2020 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com

 

 

4.2 Wiring Diagrams (Hardwired units only)

 

 

For  North American  applications, UPS  models may  be  configured for 

an 

input voltage of 208 or 240 volts at 60 Hz. SSO tap must match 
customers utility voltage. Output voltages for these models are available 

at 120, 208 (using the 120 & 88 taps) and 240 volts at 60 Hz. See the 
table below to connect to the terminal block in Figure 2-5D to achieve the 
desired input  and  output  voltage  configurations.

 

 

NORTH AMERICAN CONNECTIONS

 

 

INPUT 

OUTPUT

 

 

 

 

SSO

 

VOLTAGE 

RATING

 

VOLTAGE

 

L1 - L2 

FREQ 

VOLTAGE

 

NEURTRAL

 

BOND 

FREQ

 

TAP 

JUMPER

 

208 

208 

60 

-120     10.0 

88 

+120  

SEE

 

60 

208-(0)

 

 

240 

240 

60 

-120 

8.0 

88 

+120

 

DIAGRAM

 

 

40 

240-(0)

 

 

 
 

NOTE:

 

The neutral to ground  bond  connection  must be properly

 

connected for a  50  or 60  Hz configuration.

 

 
 

 

For  international applications, UPS  models may  be  configured for 
an input voltage of 220, 230 or 240 volts at 50 Hz. SSO tap must always 
be set to 240. Output voltage for these models matches the input voltage

 

at 50 Hz. See the table below to connect to the terminal block in Figure

 

2-5B  to achieve the  desired input  and  output  voltage  configurations.

 

 

INTERNATIONAL CONNECTIONS

 

 

INPUT 

OUTPUT

 

 

VOLTAGE 

RATING

 

 

VOLTAGE

 

L1 - L2 

FREQ 

VOLTAGE

 

 

NEURTRAL

 

BOND 

FREQ

 

 

SSO TAP 

JUMPER

 

-- 

-- 

-- 

-- 

-- 

-- 

--

 

 

220 

220 

50Hz 

-- 

110 

220

 

230  

230

  

50Hz 

-- 

115 

230

 

 
 

SEE 

DIAGRAM

 

-- 

--

 

 

50Hz 

240-(0)

 

50Hz 

240-(0)

 

240 

240 

50Hz 

-- 

120 

240 

50Hz 

240-(0)

 

Содержание SURGEX Security Plus II UPS-42100-85R

Страница 1: ...2020 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 UM Security Plus II Rev A Security Plus II Online Uninterruptible Power Supply UPS 42100 85R User Manual...

Страница 2: ...User Manual _________________________________________________________ 2020 AMETEK Electronic Systems Protection Technical Support 1 800 645 9721 ametekesp com...

Страница 3: ...anel 17 5 3 Audible Alarm 19 5 4 Single UPS Operation 20 5 5 Connect Devices to UPS 21 5 6 Charge the Batteries 21 5 7 Battery Mode Operation 22 5 8 Test the Batteries 22 5 9 Turn Off the UPS with Uti...

Страница 4: ...gen or nitrous oxide Connect your UPS power module s grounding terminal to a grounding electrode conductor The UPS is connected to a DC energy source battery The output terminals may be live when the...

Страница 5: ...UPTIBLE POWER SUPPLY 1 Before operating the UPS or connecting any load equipment please ensure the UPS is connected to a properly grounded electrical supply 2 This UPS has dangerously high voltages on...

Страница 6: ...roduces leakage current to earth on the input mains When selecting a circuit breaker for the branch circuit supplying power to the UPS ensure that the breaker selected is not an ELCB type circuit brea...

Страница 7: ...from the AC input dangerous voltage potential still exists between the battery terminal and the ground terminal 7 UPS batteries represent a high voltage source and a potential hazard to personal safet...

Страница 8: ...1778 5th Edition Safety Markings cTUVus CE EMI Conducted Emission IEC EN 62040 2 FCC PART15 CLASS A Radiated Emission IEC EN 62040 2 FCC PART15 CLASS A EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000...

Страница 9: ...check the contents The shipping package contains Quick Start Guide One UPS One RS 232 cable option One USB cable NOTE Before installation please inspect the unit Be sure that nothing inside the packag...

Страница 10: ...com 3 0 UPS PANEL LAYOUT 1 RS 232 communications port 2 USB communications port 3 Emergency power off connector EPO 4 Intelligent pocket 5 Charger cooling fan 6 Power stage cooling fan 7 Maintenance...

Страница 11: ...d only be executed by qualified professional personnel 1 Make sure the mains wire and breakers in the building are suitable for the rated capacity of the UPS to avoid the hazards of electric shock or...

Страница 12: ...the chart below are intended for installations in North America For international installations please refer to the local and national electrical codes and standards RATING INPUT CONDUCTOR AWG MIN MA...

Страница 13: ...VOLTAGE RATING VOLTAGE L1 L2 FREQ VOLTAGE NEURTRAL BOND FREQ TAP JUMPER 208 208 60 120 10 0 88 0 120 SEE 60 208 0 240 240 60 120 8 0 88 0 120 DIAGRAM 40 240 0 NOTE The neutral to ground bond connecti...

Страница 14: ...Output Output wiring 208V 120V NOTE 1 SSO Tap Selection needs to be set to match the input voltage NOTE 2 208 is obtained by using the 120 and 88 terminals NOTE 3 Make sure that the wires are connecte...

Страница 15: ...SSO Tap Selection needs to be set to match the input voltage Install a jumper between 0 208V or 0 240V NOTE 2 Split phase wiring load shall be balanced 50 50 on each side of transformer taps NOTE 3 M...

Страница 16: ...p Selection needs to be set to match the input voltage Install a jumper between 0 208V or 0 240V NOTE 2 There are 2 sets of 120V outputs Each set can carry half of the total UPS capacity NOTE 3 Make s...

Страница 17: ...t 120V Output 100 120V 45 AMP Refer to local and national electrical codes for proper installation guidelines The breaker recommendations listed in the chart above are intended for installations in No...

Страница 18: ...commended disconnect device ratings at full rated load are listed below 2 0 kVA Input 120V Output 100 120V 20 AMP 2 0 kVA Input 208 240V Output 200 240V 10 AMP 3 0 kVA Input 120V Output 100 120V 30 AM...

Страница 19: ...on more than 0 5s to turn off the UPS Esc key Press this button to return to last menu in set ting menu Test Up Button Battery test Press and hold the button more than 0 5s to test the battery while i...

Страница 20: ...45 9721 ametekesp com 5 2 LED Indicators and LCD Panel LCD panel LED indicators LED Indicators There are 4 LEDs on front panel to show the UPS working status LED Mode Bypass Line Battery Fault UPS Sta...

Страница 21: ...hours M minutes S seconds Fault Information Indicates that the warning and fault occurs Indicates the fault codes and the codes are listed in detail in section 3 9 Mute Operation Indicates that the U...

Страница 22: ...rcuit is working Indicates the ECO mode is enabled Indicates the Inverter circuit is working Indicates the output is working Battery information Indicates the Battery capacity by 0 25 26 50 51 75 and...

Страница 23: ...UPS To protect your precious devices you should turn on the UPS Refer to next step 2 Press and hold the ON button for 0 5s to turn on the UPS and the buzzer will beep once 3 A few seconds later the UP...

Страница 24: ...mended that the total loads connected to the UPS are less than 80 of its nominal power capacity 5 If the overload time is over acceptable time listed in the spec at AC mode the UPS will automatically...

Страница 25: ...ries are depleted 2 In Battery mode pressing the Mute button to disable the buzzer 3 The backup time may vary with different environment temperatures and load types 4 Battery discharge protection can...

Страница 26: ...breaker When the display panel clears the UPS is off 5 10 Turn Off the UPS Without Utility Power Supply in Battery Mode 1 Turn off the UPS by pressing OFF button for at least 0 5s and then the buzzer...

Страница 27: ...buzzer beeps continuously it means that there is a fatal error in the UPS Check the troubleshooting table in Section 8 for a list of fault codes 2 If still problem still exists contact SurgeX Technica...

Страница 28: ...ttery 01 Output voltage Y 02 Output frequency Y 03 Voltage range for bypass Y 04 Frequency range for bypass Y 05 ECO mode enable disable Y 06 Voltage range for ECO mode Y 07 ECO mode frequency range s...

Страница 29: ...ed only when UPS shuts down normally with internal or external battery connection Normal UPS shutdown means turning off input breaker in bypass no output mode 01 Output Voltage Interface Setting Param...

Страница 30: ...UPS to normal mode not CVCF mode If selected the output frequency will synchronize with the input frequency within 46 54 Hz UPS will transfer to battery mode when input frequency is not within 46 54...

Страница 31: ...y HS Set the acceptable high voltage for bypass Setting range is from 231V to 276V and the default value is 264V 04 Frequency Range for Bypass Interface Setting Parameter 1 2 Setting acceptable freque...

Страница 32: ...n is enabled 06 Voltage Range for ECO Mode Interface Setting Parameter 1 2 Setting acceptable voltage range for ECO mode Set up the range by setting high and low points When it shows LLS in parameter...

Страница 33: ...z to 58 0Hz The default value is 48 0Hz 58 0Hz Pressing Enter key to confirm the setting value for low point Then it will show HS in parameter 1 Set up high point in parameter 2 by pressing Up or Down...

Страница 34: ...ection and backup time will depend on battery capacity The default value is DIS 10 Reserved Interface Setting Reserved 11 Reserved Interface Setting Reserved 12 Hot Standby Function Enable disable Int...

Страница 35: ...ameter 2 the voltage range is from 0V to 5 7V the default value is 0V 14 Charger Voltage Adjustment Interface Setting After it shows 14 in parameter 1 please press Enter key first Then you may choose...

Страница 36: ...Then you may choose Ad or SU to adjust output voltage in Parameter 1 by pressing Up or Down key After pressing Enter key to confirm your selection it will jump to parameter 2 to set up the value Param...

Страница 37: ...n the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery at AC mode ECO Mode When the input voltage is within voltage reg...

Страница 38: ...d alarm will beep every 4 seconds Bypass Mass When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two min utes Battery...

Страница 39: ...er soft start failure 11 None Over temperature 41 None High Inverter voltage 12 None CPU communication failure 42 None Low Inverter voltage 13 None Overload 43 Inverter output short circuited 14 Batte...

Страница 40: ...very second I P fuse broken Beeping every second Overload 3 times in 30min Beeping every second 8 2 Warning Code Warnin g Cod e Warning Event Warning Code Warning Event 0 1 Battery unconnected 10 L1 I...

Страница 41: ...ction The icon and flash on LCD display and alarm beeps every second The external or internal battery is incorrectly connected Check if all batteries are connected well The icon and flash on LCD displ...

Страница 42: ...03 04 11 12 13 14 1A 21 24 35 36 41 42 or 43 on LCD display and alarm beeps continuously A UPS internal fault has occurred There are two possible results 1 The load is still sup plied but directly fr...

Страница 43: ...TION The UPS system operates with hazardous voltages Repairs may be carried out only by qualified maintenance personnel CAUTION Even after the unit is disconnected from the mains components inside the...

Страница 44: ...current Please remove all wristwatches rings and other metal personal objects before maintenance or repair and only use tools with insulated grips and handles for maintaining or repairing CAUTION Whe...

Отзывы: