Installation Guide
9 - 5
Thermal Imaging System
NIR-B Borescope
Electrical Auto Retract
9.3.1 Changing the time delay for the water sensor
1)
Ensure the ECU is powered up and the PLC is running.
2)
Using the arrow keys on the SIEMENS LOGO PLC, press the
DOWN
arrow until the
following screen is displayed (Fig. 9-7).
Fig. 9-7 Siemens LOGO PLC
3)
Press the
ESC
key. and navigate down to the option
Set Param
and press
OK
.
4)
Using the
UP
/
DOWN
arrows, select
Program
and press
OK
.
Fig. 9-8 Program option
5)
Using the
UP
/
DOWN
arrows, select
Set Parameter
and press
OK
.
Fig. 9-9 Set Parameter option