52
IMPORTANT:
The “A” and “B” Factors have been preprogrammed by the factory, but can
be changed in the field. If the Phase 7 OPL microprocessor controller (computer)
should fail and is being replaced.
THE REPLACEMENT PHASE 7 OPL
MICROPROCESSOR CONTROLLER (COMPUTER) MUST BE
REPROGRAMMED FOR THE SPECIFIC MODEL SHOWN IN THE “A” and
“B” FACTOR PARAMETERS CHART ON THE PREVIOUS PAGE (page 51).
The “A” “B” FACTOR LABEL IS LOCATED IN THE TOP CONTROL PANEL,
BEHIND THE PHASE 7 KEYPAD-DISPLAY DOOR.
NOTE:
For fine tuning the Auto Cycle for certain loads. If cloths come out wet, then
decrease
the “B” Factor, if cloths come out too dry,
increse
the “B” Factor.