18
b. Outside Ductwork Protection
1) To protect the outside end of the horizontal ductwork from the weather, a 90° elbow bent downward
should be
installed where the exhaust exits the building. If the exhaust ductwork travels vertically
up through the roof, it
should be
protected from the weather by using a 180° turn to point the
opening downward. In either case, allow at least twice the diameter of the duct between the duct
opening and nearest obstruction.
IMPORTANT:
DO NOT
use screens, louvers, or caps on the outside opening of the exhaust
ductwork.
3. Multiple Dryer (Common) Venting
If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be
channeled into a common main duct. The individual ducts should enter the bottom or side of the main
duct at an angle not more than 45° in the direction of airflow and
should be
spaced at least 48-3/4 (123.8
cm) apart. The main duct
should be
tapered, with the diameter increasing before each individual 16-inch
(40.64 cm) duct is added.
a. Multiple Dryer Venting
1) In case of multiple (common) dryer venting, the distance from the last dryer to the outside exhaust
outlet
must not
exceed
20 feet (6.1 meters), and not have more than one (1) elbow (including
outside protection).
2) The minimum size of the duct from each dryer into the common duct is 16-inches (40.64 cm), and
must not have more than one (1) elbow. The total duct run from the dryer to the common duct
must not exceed
15 feet (4.57 meters) in length.
IMPORTANT:
This dryer
is not
provided with a back draft damper. When exhausted into a multiple
(common) exhaust line, a back draft damper
must be
installed at each dryer duct.
IMPORTANT:
No more than four (4) dryers
should be
connected to one (1) main common duct.
The main duct may be any shape or cross-sectional area, so long as the minimum cross section area
is provided. The
illustration
on
page 19
shows the minimum cross-sectional area for multiple
dryer round or square venting. These figures
must be
increased 10 square inches (64.52 square
centimeters) when rectangular main ducting is used, and the ratio of duct width to depth
should not
be
greater than 3-1/2 to 1. These figures
must be
increased in proportion if the main duct run to
the last dryer to where it exhausts to the outdoors exceeds the maximum limits noted.
IMPORTANT:
For extended ductwork runs, the cross section area of the ductwork can only be
increased to an extent. Maximum proportional ductwork runs
cannot
exceed 20 feet
(6.1 meters) more than the original limitations of 20 feet (6.1 meters) with two (2)
elbows. When the ductwork approaches the maximum limits as noted in this manual,
a professional heating, venting, and air conditioning (HVAC) firm
should be
consulted
for proper venting information.
Содержание Gas/HSI & Steam ID-120
Страница 54: ...ADC113330 1 08 31 01 25 ...