![Amana PTC073E Series Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/amana/ptc073e-series/ptc073e-series_service-instructions-manual_2916143009.webp)
9
SPECIFICATIONS
@ 230V @ 208V @ 265V
230/208V
2.5
1
8,500
6,800
- -
2,570 / 2,115
11.2 / 10.1
14.0
15
6-1 5 P
230/208V
3.5
1
12,000
9,900
- -
3,570 / 2,935
15.5 / 14.1
19.4
20
6-2 0 P
230/208V
5
1
17,100
14,000
- -
5,070 / 4,160
22.1 / 20.0
27.5
30
6-3 0 P
265V
2.5
1
- -
- -
8,500
2,570
9.7
12.1
15
7-2 0 P
265V
3.7
1
- -
- -
12,600
3,770
14.2
17.8
20
7-2 0 P
265V
5
1
- -
- -
17,100
5,070
19.2
23.9
25
7-3 0 P
Nominal Heating (BTU/h)
Power Cord
Total
Watts
6
Total
Amps
Min. Circuit
Ampacity²
MOD
4
(amps)
Voltage
Electric
Heater Size
(kW)
No. of
Stages
Notes:
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
³ Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
5
Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.
7
Specify two-digit heater kW size to complete model number.
8
R-410A refrigerant used in all systems.
9
All units meet or exceed ASHRAE 90.1 standards.
10
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
4
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay
fuses (included and factory-installed on all Amana® brand 265-volt chassis).
6
Total watts for 15,000 BTU/h models; subtract 20 watts for PT07/09/12
ELECTRIC HEAT PERFORMANCE
EER -
Energy Efficiency Ratio per The Air-Conditioning,
Heating, and Refrigeration Institute (AHRI) Test
Procedures and Canadian Standards Association
(CSA) Test Procedures.
COP -
Coefficient of Performance per AHRI Test
Procedures
PTC***(E,F,G) & PTH***(E,F) Models
DRY***(E, G) Models