20
SPECIFICATIONS
WIRING
CAUTION
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH DUE TO ELECTRICAL SHOCK:
• DO NOT USE AN EXTENSION CORD WITH THIS UNIT.
• USE ONLY COPPER CONDUCTORS.
• WIRING TO THE UNIT MUST BE PROPERLY POLAR-
IZED AND GROUNDED.
Cord connection to a wall socket is not permitted for 265-
volt units. All 265-volt units must be hard wired using the
hard wire kit or make use of the plug-in receptacle in the
standard subbase.
Heaterless Units
If a heaterless unit is ordered, field provisions must be made
for supplemental heat if desired. Refer to the Installation
Instructions supplied with the heater kit for a complete de-
scription of the installation procedures. All 208/230 volt
heaterless units are shipped with a 15 Amp power cord and
all heaterless 265 volt units are shipped with a 20 Amp power
cord.
When adding a heater kit to a unit, the power cord supplied
with the heater kit must be used in place of the power cord
supplied with the unit. The following table specifies power
cord rating requirements for the various heater kits.
230/208 Volt Units
265 Volt Units
Power Cord Rating
(amp)
Power Cord Rating
(amp)
1.5
15
20
2.5
15
20
3.5
20
Not Applicable
3.7
Not Applicable
20
5
30
30
POWER CORD REQUIREMENTS
Heater Size
(kW)
NOTE
: Heaterless units are shipped with an auxiliary data
label on the front side of the mid-partition panel. If an
electric heater kit is field installed, the installer must mark
the appropriate box on the label to indicate the electric
heater capacity. If no heater is installed, the box labeled
“None” must be marked. Refer to the unit nameplate for
over current protection data.
CAUTION
DO NOT INSTALL A 5kW HEATER KIT IN ANY 7,000
OR 9,000 BTU CHASSIS.
OPERATING CONTROLS
Users Controls
Two rotary knobs controlling temperature and operational
ON / OFF
MASTER SWITCH
M2
M1
SW2
P10
COM A
P12
P13
IAT
BLACK
DS1 DS2 MS1 MS2 EH IN
LS FD1 FD2 TF- TF+ C
R
GL W2 Y/W1 B
GH
REMOTE THERMOSTAT
AUXILIARY
Mode
Switches
Master Switch
The master switch disconnects power to all of the system
components. When this switch is in the off position, the
compressor, fan motor, reversing valve, and electric resis-
tance heater will all be de-energized.
REMOTE/STANDARD
The remote/standard configuration is used to change the
control of the unit from the standard on board controls in
the standard mode, to a remote wall mounted thermostat
in the remote mode. For remote control configuration set-
tings, refer to
Configuration Settings.
PROPER INSTALLATION