SPECIFICATIONS
PTC G SERIES
COOLING - PTC
PTC
PTC
PTC
PTC
PTC
PTC
PTC
072G**XXX
073G***XXX
092G**XXX
093G***XXX
123G***XXX
153G***XXX
173G**XXX
115
230 / 208
115
230 / 208
230 / 208
230 / 208
230/208
Capacity (BTU/h)
7,000
7,700 / 7,700
9000
9,000 / 9,000
11,700 / 11,500 15,000 / 14,700
16400/16200
6.9
3.5 / 3.5
8.3
4.1 / 4.1
5.6 / 5.6
7.0 / 7.0
8.4
585
670 / 660
795
805 / 785
1,135 / 1,105
1,500 / 1,470
1740/1720
EER
11.9
11.5 / 11.7
11.3
11.2 / 11.5
10.3 / 10.4
10.0 / 10.0
9.4
Unit without Electric Heater
8.3
4.2
10.1
4.9
6.8
8.5
10.2
High
290
290
290
290
290
340
340
Low
264
264
264
264
264
314
314
High
310
310
310
310
310
360
360
Low
282
282
282
282
282
332
332
65*
65*
65*
65*
65*
65*
65*
(Compressor & Fan)*
6*
6*
6*
6*
6*
6*
6*
1.7
1.7
2.3
2.2
3.6
4.4
4.8
98
98
102
102
102
113
113
113
113
117
117
119
130
130
Min. Circuit Amps ²,
4
,
10
Ventilated Air, CFM (Fan Only)*
CFM (Cool/Wet Coil)
Ship Weight (lbs.)
Am ps
10
Watts
10
Voltage ¹, ³
Model ¹,
6
,
8
,
9
Dehum idification (Pints/Hr.)
Net Weight (lbs.)
CFM (Dry Coil)
Ventilated Air, CFM
* Actual vent CFM performance will vary due to application and installation conditions.
Notes:
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
³ Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
5
Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.
6
Specify two-digit heater kW size to complete model number.
7
R-410A refrigerant used in all systems.
8
All units meet or exceed ASHRAE 90.1 standards.
9
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
10
Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.
4
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay fuses
(included and factory-installed on all Amana® brand 265-volt chassis). See heater performance for total MCA.
EER -
Energy Efficiency Ratio per The Air-Conditioning,
Heating, and Refrigeration Institute (AHRI) Test
Procedures and Canadian Standards Association
(CSA) Test Procedures.
COP -
Coefficient of Performance per AHRI Test
Procedures
PTC
PTC
PTC
PTC
074G***XXX
094G***XXX
124G***XXX
154G***XXX
265
265
265
265
Capacity (BTU/h)
7,700
9,000
12,000
14,800
3.0
3.6
4.8
6.0
670
795
1,165
1,480
EER
11.5
11.3
10.3
10.0
Unit without Electric Heater
3.6
4.4
5.9
7.4
High
290
290
290
340
Low
264
264
264
314
High
310
310
310
360
Low
282
282
282
332
65*
65*
65*
65*
(Compressor & Fan)*
6*
6*
6*
6*
1.7
2.2
3.6
4.4
98
102
102
113
113
117
119
130
Ship Weight (lbs.)
Amps
10
Watts
10
Voltage ¹, ³
Model ¹,
6
,
8
,
9
Dehumidification (Pints/Hr.)
Net Weight (lbs.)
CFM (Dry Coil)
Ventilated Air, CFM
Min. Circuit Amps ²,
4
,
10
Ventilated Air, CFM (Fan Only)*
CFM (Cool/Wet Coil)