background image

26

XIII. CIRCULATING AIR & FILTERS

D

UCTWORK

 - A

IR

 F

LOW

Duct systems and register sizes must be properly designed for the
CFM  and  external  static  pressure  rating  of  the  furnace.  Ductwork
should  be  designed  in  accordance  with  the  recommended  meth-
ods of   “Air Conditioning Contractors of America” Manual D.

A duct  system  must  be  installed  in  accordance  with  Standards  of
the  National  Board  of  Fire  Underwriters  for  the  Installation  of  Air
Conditioning,  Warm  Air  Heating  and  Ventilating  Systems.  Pam-
phlets No. 90A and 90B.

A  closed  return  duct  system  must  be  used,  with  the  return  duct
connected to the furnace. NOTE:  Ductwork must never be attached
to  the  back  of  the  furnace.

  

Supply and  return  connections  to  the

furnace may be made with flexible joints to reduce noise transmis-
sion. To prevent the blower from interfering with combustion air or
draft  when  a  central  return  is  used,  a  connecting  duct  must  be
installed between the unit and the utility room wall.  A room, closet,
or alcove must not be used as a return air chamber.

When  the  furnace  is  used  in  connection  with  a  cooling  unit,  the
furnace should be installed in parallel with or on the upstream side
of  the  cooling  unit  to  avoid  condensation  in  the  heating  element.
With  a  parallel  flow  arrangement,  the  dampers  or  other  means
used to control the flow of air must be adequate to prevent chilled
air  from  entering  the  furnace  and,  if  manually  operated,  must  be
equipped with means to prevent operation of either unit unless the
damper is in the full heat or cool position.

When  the  furnace  is  installed  without  a  cooling  coil,  it  is  recom-
mended  that  a  removable  access  panel  be  provided  in  the  outlet
air  duct.   This  opening  shall  be  accessible  when  the  furnace  is
installed and shall be of such a size that the heat exchanger can be
viewed  for  visual  light  inspection  or  such  that  a  sampling  probe
can  be  inserted  into  the  airstream.   The  access  panel  must  be
made to prevent air leaks when the furnace is in operation.

When the furnace is heating, the temperature of the return air en-
tering the furnace must be between 55°F and 100°F.

F

ILTERS

 - R

EAD

 T

HIS

 S

ECTION

 B

EFORE

 I

NSTALLING

 T

HE

R

ETURN

 A

IR

 D

UCTWORK

Filters  must  be used  with  this  furnace. Discuss  filter  maintenance
with  the  building  owner.   Filters  do  not  ship  with  this  furnace,  but
must be provided by the installer. Filters must comply with UL900
or  CAN/ULCS111  standards.  If  the  furnace  is  installed  without  fil-
ters, the warranty will be voided.

On upflow units, guide dimples locate the side  return cutout
locations.  Use a straight edge to scribe lines connecting the
dimples.   Cut  out  the  opening  on  these  lines.   NOTE:  An
undersized opening will cause reduced airflow.

Refer to Minimum Filter Area tables to determine filter area require-
ments.

600

800

1000

1200

1400

1600

2000

0453BXA

194*

194*

240

288

---

---

---

0703BXA

---

324*

324*

324*

336

---

---

0704CXA

---

---

291*

291*

336

384

---

0904CXA

---

---

432*

432*

432*

432*

---

0905DXA

---

---

---

388*

388*

388*

480

1155DXA

---

---

---

486*

486*

486*

486*

In

p

u

t_

_

A

ir

fl

o

w

COOLING AIRFLOW REQUIREMENT (CFM)

*Minimum  filter  area  dictated  by heating  airflow requirement.

Permanent Minimum Filter Area (sq. in)

[Based on a 600 ft/min filter face velocity]

600

800

1000

1200

1400

1600

2000

0453B XA

388*

388*

480

576

---

---

---

0703B XA

---

647*

647*

647*

672

---

---

0704CXA

---

---

583*

583*

672

768

---

0904CXA

---

---

863*

863*

863*

863*

---

0905DXA

---

---

---

777*

777*

777*

960

1155DXA

---

---

---

971*

971*

971*

971*

In

p

u

t_

_

A

ir

fl

o

w

COO LING  AIRFLO W  REQ UIREM ENT  (CFM )

*Minimum  filter  area  dictated  by heating  airflow requirement.

Disposable Minimum Filter area (sq. in)

[Based on 300 ft/min filter face velocity]

U

PRIGHT

 I

NSTALLATIONS

Depending  on  the  installation  and/or  customer  preference,  differ-
ing  filter arrangements  can be  applied.   Filters can  be installed  in
the  central  return  register  or  a  side  panel  external  filter  rack  kit
(upflows).  As an alternative a media air filter or electronic air cleaner
can be used as the requested filter.

The  following  figure  shows  possible  filter  locations.

F

IL

T

E

R

AIR FLOW

CENTRAL

RETURN

GRILLE

F

IL

T

E

R

SIDE RETURN

EXTERNAL FILTER

RACK KIT

(EITHER SIDE)

  

FIL

TE

R

F

IL

T

E

R

AIR FLOW

FILTER

ACCESS 

DOOR

CENTRAL

RETURN

GRILLE

RETURN

DUCT

FI

LT

E

R

FILTER

SUPPORT
BRACKET

(PROVIDED)

Possible  Upright  Upflow

Possible  Upright  Counterflow

Filter Locations

NOTE:  Internal filter retention is not provided on this furnace.  If an
internal installation is desired, an internal filter retention kit is avail-
able as an accessory.   Please see your distributor for details.

Содержание AMS95

Страница 1: ...is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to b...

Страница 2: ...D JOINING METHODS 12 PROPER VENT FLUE AND COMBUSTION AIR PIPING PRACTICES 13 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 13 STANDARD FURNACE CONNECTIONS 13 ALTERNATE FURNACE CONNECTIONS 14...

Страница 3: ...ty Circuit Description 31 GENERAL 31 INTEGRATED CONTROL MODULE 31 PRIMARY LIMIT 31 AUXILIARY LIMIT 31 ROLLOUT LIMIT 31 PRESSURE SWITCHES 31 FLAME SENSOR 31 XVIII Troubleshooting 31 ELECTROSTATIC DISCH...

Страница 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty cer tificate in a safe location for future reference If additional informatio...

Страница 5: ...r Pressure Tap 20 Coil Front Cover Drain Port 21 Drain Line Penetrations 22 Drain Trap 23 Blower Door Interlock Switch 24 Capacitor 25 Integrated Control Module with fuse and diagnostic LED 26 24 Volt...

Страница 6: ...ing to the installation and application of this product WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSTAION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY...

Страница 7: ...e access doors must be vertical so that the burners fire horizontally into the heat exchanger Do not install the unit with the access doors on the up top or down bottom side of the furnace WARNING TO...

Страница 8: ...reas behind the thermostat such as an outside wall CLEARANCES AND ACCESSIBILITY Installations must adhere to the clearances to combustible mate rials to which this furnace has been design certified Th...

Страница 9: ...less than 100 square inches One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure DRAFTS OR DEAD SPOTS BEHIND DOORS IN CORNERS UNDER CABINETS Thermo...

Страница 10: ...equip ment in the enclosure but not less than the sum of the areas of all vent connectors in the confined space Alternate Opening Location Equipment Located in Confined Spaces All Air from Outdoors Si...

Страница 11: ...RAL Horizontal applications in particular may dictate many of the installation s specifics such as airflow direction ductwork connec tions flue and combustion air pipe connections etc The basic ap pli...

Страница 12: ...ce change to compensate for the energy content difference between natural and propane gas High altitude installations may require both a pressure switch and an orifice change These changes are necessa...

Страница 13: ...vent flue pipe and a combustion air intake pipe Refer to the appropriate section for details concerning piping size length number of elbows furnace connections and terminations MATERIALS AND JOINING M...

Страница 14: ...DIRECT VENT INSTALLATIONS On upflow units secure the combustion air intake pipe directly to the air intake coupling On counterflow units secure the combus tion air intake pipe to the air intake coupl...

Страница 15: ...e piping to the rubber elbow using a worm gear hose clamp NOTE Use of the alternate vent flue location for upright installations requires the drain trap be installed on the same side of the unit as th...

Страница 16: ...uld be in stalled on either side of the wall and solvent cemented to a length of pipe connecting the two couplings The length of pipe should be the wall thickness plus the depth of the socket fittings...

Страница 17: ...er of elbows and or tees in each Vent Flue Combustion Air Intake pipe Elbows and or tees used in the terminations must be included when determining the number of elbows in the piping systems If the co...

Страница 18: ...ualPipe In a basement installation the pipes may be run between the joist spaces If the pipes must go below the joist and then up into the last joist space to penetrate the header two 45 elbows should...

Страница 19: ...stallations using the standard vent flue outlet require drain hoses to be connected as follows The following quantity of hoses tubes and hose clamps are provided with the unit HOSE A QTY 1 HOSE B QTY...

Страница 20: ...ow models relocation of the front cover pressure switch hose is required Make connections as follows 1 Remove the rubber plug from the coil front cover drain port Counterflow furnaces Relocate the fro...

Страница 21: ...ed for identification purposes Refer to the wiring dia gram for wire routings If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring ma terial having...

Страница 22: ...CHANGING ANY ELECTRICAL WIRING The furnace s integrated control module is equipped with line volt age accessory terminals for controlling power to an optional field supplied humidifier and or electro...

Страница 23: ...it must be applied for propane gas installations Refer to the Section VIII Propane Gas High Altitude Installations section for details GAS VALVE This unit is equipped with a 24 volt gas valve controll...

Страница 24: ...s and semirigid tubing against physical and thermal damage when installed Ensure aluminum alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry plas...

Страница 25: ...ace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the liquid and wetted surface area of th...

Страница 26: ...0 F FILTERS READ THIS SECTION BEFORE INSTALLING THE RETURN AIR DUCTWORK Filters must be used with this furnace Discuss filter maintenance with the building owner Filters do not ship with this furnace...

Страница 27: ...e the burner compartment door 9 Open the manual gas shutoff valve external to the furnace 10 Turn on the electrical power to the furnace 11 Adjust the thermostat to a setting above room temperature 12...

Страница 28: ...VENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATO...

Страница 29: ...Temperature rise must be within the range specified on the unit rating plate An incorrect temperature rise may result in condens ing in or overheating of the heat exchanger An airflow and tem perature...

Страница 30: ...ized Circulator blower is energized on cool speed following a fixed five second on delay Electronic air cleaner terminals are energized with circulator blower Furnace circulator blower and outdoor coo...

Страница 31: ...heat exchanger and or blocked condensate drain con ditions FLAME SENSOR The flame sensor is a probe mounted to the burner manifold as sembly which uses the principle of flame rectification to determin...

Страница 32: ...power to furnace MEDIA AIR FILTER OR ELECTRONIC AIR CLEANER REMOVAL Follow the manufacturer s directions for service BURNERS Visually inspect the burner flames periodically during the heating season...

Страница 33: ...t Filter Front of Furnace Blower 4 Angle filter toward the blower until filter clears bottom rail 5 Lower filter down and pull outward Front of Furnace Blower Front of Furnace Blower 6 Replace filter...

Страница 34: ...ecessary Correct pressure switch setpoint or contact motion Tighten or correct wiring connection Pressure switch hose blocked pinched or connected improperly Blocked flue and or inlet air pipe blocked...

Страница 35: ...nfo Adjust as Turn power OFF prior to repair Sand flame sensor with emery clot See Vent Flue Pipe section for piping details See rating plate for proper gas pressure 7 7 FLASHES Flame sensor is coated...

Страница 36: ...EC T L N P O W E R S U P P L Y W I T H O V E R C U R R E N T P R O T E C T I O N D E V I C E WH JUNCTION BOX 1 T O 1 1 5 V A C 1 0 6 0 H Z ID BLOWER PRSEEURE SWITCH HEAT H GND WH RD WH GND BURNER COM...

Страница 37: ...37 2005 Goodman Company L P is a trademark of Maytag Corporation and is used under license to Goodman Company L P All rights reserved 1810 Wilson Parkway Fayetteville TN 37334 www amana hac com...

Отзывы: