23

CAUTION

T

O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE INLET

GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE

WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING.

Inlet gas supply pressures must be maintained within the ranges
specified below.  The supply pressure must be constant and avail-
able with all other household gas fired appliances operating.  The
minimum gas supply pressure must be maintained to prevent unre-
liable ignition.  The maximum must not be exceeded to prevent unit
overfiring.

Propane Gas

Natural Gas

Inlet Gas Supply Pressure

Minimum:5.0" W.C.   Maximum :10.0" W.C.
Minimum:11.0" W.C. Maximum :13.0" W.C.

H

IGH

 A

LTITUDE

 D

ERATE

When this furnace is installed at high altitude, the appropriate High
Altitude orifice kit must be applied.  This is required due to the
natural reduction in the density of both the gas fuel and combus-
tion air as altitude increases.  The kit will provide the proper design
certified input rate within the specified altitude range.
High altitude kits are purchased according to the installation alti-
tude and usage of either natural or propane gas.  Contact your
distributor for a tabular listing of appropriate altitude ranges and
corresponding manufacturer’s high altitude (Natural, Propane Gas,
and/or Pressure Switch) kits.
Do 

not

 derate the furnace by adjusting the manifold pressure to a

lower pressure than specified on the furnace rating plate.  The
combination of the lower air density and a lower manifold pressure
will prohibit the burner orifice from drawing the proper amount of
air into the burner.  This may cause incomplete combustion, flash-
back, and possible yellow tipping.
In some areas the gas supplier may artificially derate the gas in an
effort to compensate for the effects of altitude.  If the gas is artifi-
cially derated, the appropriate orifice size must be determined
based upon the BTU/ft

3

 content of the  derated gas and the altitude.

Refer to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and
information provided by the gas supplier to determine the proper
orifice size.
A different pressure switch may be required at high altitude regard-
less of the BTU/ft

3

 content of the fuel used.  Contact your distributor

for a tabular listing of appropriate altitude ranges and correspond-
ing manufacturer’s pressure switch kits.

P

ROPANE

 G

AS

 C

ONVERSION

WARNING

P

OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR IF

THE CORRECT CONVERSION KITS ARE NOT INSTALLED. 

T

HE APPROPRIATE KITS

MUST BE APPLIED TO INSURE SAFE AND PROPER FURNACE OPERATION. 

A

LL

CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE
AGENCY.

This unit is configured for natural gas.  The appropriate
manufacturer’s propane gas conversion kit, must be applied for
propane gas installations.  Refer to the 

Section VIII, Propane Gas

/ High Altitude Installations

 section for details.

G

AS

 V

ALVE

This unit is equipped with a 24 volt gas valve controlled during
furnace operation by the integrated control module.  As shipped,
the valve is configured for natural gas.  The valve is field convertible

for use with propane gas by replacing the regulator spring with a
propane gas spring from an appropriate manufacturer’s propane
gas conversion kit.  Taps for measuring the gas supply pressure
and manifold pressure are provided on the valve.
The gas valve has a manual ON/OFF control located on the valve
itself.  This control may be set only to the “ON” or “OFF” position.
Refer to the lighting instructions label or 

Section XIV, Startup Pro-

cedure & Adjustment 

for use of this control during start up and shut

down periods.

G

AS

 P

IPING

 C

ONNECTIONS

G

ENERAL

CAUTION

T

O AVOID POSSIBLE UNSATISFACTORY OPERATION OR EQUIPMENT DAMAGE

DUE TO UNDERFIRING OF EQUIPMENT, USE THE PROPER SIZE OF
NATURAL/PROPANE GAS PIPING NEEDED WHEN RUNNING PIPE FROM THE

METER/TANK TO THE FURNACE.

When sizing a trunk line, be sure to include all appliances which
will operate simultaneously when sizing a trunk line.
The gas piping supplying the furnace must be properly sized based
on the gas flow required, specific gravity of the gas, and length of
the run.  The gas line installation must comply with local codes, or
in their absence, with the latest edition of the National Fuel Gas
Code, NFPA 54/ANSI Z223.1.

Natural Gas Capacity of Pipe

In Cubic Feet of Gas Per Hour (CFH)

Length of

Nominal Black  Pipe Size

Pipe in Feet

1/2"

3/4"

1"

1 1/4"

1 1/2"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specific Gravity Gas)

CFH = BTUH Furnace Input   

Heating Value of Gas (BTU/Cubic Foot)

To connect the furnace to the building’s gas piping, the installer
must supply a ground joint union, drip leg, manual shutoff valve,
and line and fittings to connect to gas valve.  In some cases, the
installer may also need to supply a transition piece from 1/2" pipe
to a larger pipe size.
The following stipulations apply when connecting gas piping.  Re-
fer to 

Gas Piping Connections 

figure for typical gas line connec-

tions to the furnace.

Use black iron or steel pipe and fittings for building piping.
Where possible, use new pipe that is properly chamfered,
reamed, and free of burrs and chips.  If old pipe is used, be
sure it is clean and free of rust, scale, burrs, chips, and old
pipe joint compound.

Use pipe joint compound on male threads ONLY.  Always
use pipe joint compound (pipe dope) that is APPROVED
FOR ALL GASSES.  DO NOT apply compound to the first two
threads.

Use ground joint unions.

Содержание AMS95

Страница 1: ...is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to b...

Страница 2: ...D JOINING METHODS 12 PROPER VENT FLUE AND COMBUSTION AIR PIPING PRACTICES 13 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 13 STANDARD FURNACE CONNECTIONS 13 ALTERNATE FURNACE CONNECTIONS 14...

Страница 3: ...ty Circuit Description 31 GENERAL 31 INTEGRATED CONTROL MODULE 31 PRIMARY LIMIT 31 AUXILIARY LIMIT 31 ROLLOUT LIMIT 31 PRESSURE SWITCHES 31 FLAME SENSOR 31 XVIII Troubleshooting 31 ELECTROSTATIC DISCH...

Страница 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty cer tificate in a safe location for future reference If additional informatio...

Страница 5: ...r Pressure Tap 20 Coil Front Cover Drain Port 21 Drain Line Penetrations 22 Drain Trap 23 Blower Door Interlock Switch 24 Capacitor 25 Integrated Control Module with fuse and diagnostic LED 26 24 Volt...

Страница 6: ...ing to the installation and application of this product WARNING POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSTAION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY...

Страница 7: ...e access doors must be vertical so that the burners fire horizontally into the heat exchanger Do not install the unit with the access doors on the up top or down bottom side of the furnace WARNING TO...

Страница 8: ...reas behind the thermostat such as an outside wall CLEARANCES AND ACCESSIBILITY Installations must adhere to the clearances to combustible mate rials to which this furnace has been design certified Th...

Страница 9: ...less than 100 square inches One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure DRAFTS OR DEAD SPOTS BEHIND DOORS IN CORNERS UNDER CABINETS Thermo...

Страница 10: ...equip ment in the enclosure but not less than the sum of the areas of all vent connectors in the confined space Alternate Opening Location Equipment Located in Confined Spaces All Air from Outdoors Si...

Страница 11: ...RAL Horizontal applications in particular may dictate many of the installation s specifics such as airflow direction ductwork connec tions flue and combustion air pipe connections etc The basic ap pli...

Страница 12: ...ce change to compensate for the energy content difference between natural and propane gas High altitude installations may require both a pressure switch and an orifice change These changes are necessa...

Страница 13: ...vent flue pipe and a combustion air intake pipe Refer to the appropriate section for details concerning piping size length number of elbows furnace connections and terminations MATERIALS AND JOINING M...

Страница 14: ...DIRECT VENT INSTALLATIONS On upflow units secure the combustion air intake pipe directly to the air intake coupling On counterflow units secure the combus tion air intake pipe to the air intake coupl...

Страница 15: ...e piping to the rubber elbow using a worm gear hose clamp NOTE Use of the alternate vent flue location for upright installations requires the drain trap be installed on the same side of the unit as th...

Страница 16: ...uld be in stalled on either side of the wall and solvent cemented to a length of pipe connecting the two couplings The length of pipe should be the wall thickness plus the depth of the socket fittings...

Страница 17: ...er of elbows and or tees in each Vent Flue Combustion Air Intake pipe Elbows and or tees used in the terminations must be included when determining the number of elbows in the piping systems If the co...

Страница 18: ...ualPipe In a basement installation the pipes may be run between the joist spaces If the pipes must go below the joist and then up into the last joist space to penetrate the header two 45 elbows should...

Страница 19: ...stallations using the standard vent flue outlet require drain hoses to be connected as follows The following quantity of hoses tubes and hose clamps are provided with the unit HOSE A QTY 1 HOSE B QTY...

Страница 20: ...ow models relocation of the front cover pressure switch hose is required Make connections as follows 1 Remove the rubber plug from the coil front cover drain port Counterflow furnaces Relocate the fro...

Страница 21: ...ed for identification purposes Refer to the wiring dia gram for wire routings If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring ma terial having...

Страница 22: ...CHANGING ANY ELECTRICAL WIRING The furnace s integrated control module is equipped with line volt age accessory terminals for controlling power to an optional field supplied humidifier and or electro...

Страница 23: ...it must be applied for propane gas installations Refer to the Section VIII Propane Gas High Altitude Installations section for details GAS VALVE This unit is equipped with a 24 volt gas valve controll...

Страница 24: ...s and semirigid tubing against physical and thermal damage when installed Ensure aluminum alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry plas...

Страница 25: ...ace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the liquid and wetted surface area of th...

Страница 26: ...0 F FILTERS READ THIS SECTION BEFORE INSTALLING THE RETURN AIR DUCTWORK Filters must be used with this furnace Discuss filter maintenance with the building owner Filters do not ship with this furnace...

Страница 27: ...e the burner compartment door 9 Open the manual gas shutoff valve external to the furnace 10 Turn on the electrical power to the furnace 11 Adjust the thermostat to a setting above room temperature 12...

Страница 28: ...VENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATO...

Страница 29: ...Temperature rise must be within the range specified on the unit rating plate An incorrect temperature rise may result in condens ing in or overheating of the heat exchanger An airflow and tem perature...

Страница 30: ...ized Circulator blower is energized on cool speed following a fixed five second on delay Electronic air cleaner terminals are energized with circulator blower Furnace circulator blower and outdoor coo...

Страница 31: ...heat exchanger and or blocked condensate drain con ditions FLAME SENSOR The flame sensor is a probe mounted to the burner manifold as sembly which uses the principle of flame rectification to determin...

Страница 32: ...power to furnace MEDIA AIR FILTER OR ELECTRONIC AIR CLEANER REMOVAL Follow the manufacturer s directions for service BURNERS Visually inspect the burner flames periodically during the heating season...

Страница 33: ...t Filter Front of Furnace Blower 4 Angle filter toward the blower until filter clears bottom rail 5 Lower filter down and pull outward Front of Furnace Blower Front of Furnace Blower 6 Replace filter...

Страница 34: ...ecessary Correct pressure switch setpoint or contact motion Tighten or correct wiring connection Pressure switch hose blocked pinched or connected improperly Blocked flue and or inlet air pipe blocked...

Страница 35: ...nfo Adjust as Turn power OFF prior to repair Sand flame sensor with emery clot See Vent Flue Pipe section for piping details See rating plate for proper gas pressure 7 7 FLASHES Flame sensor is coated...

Страница 36: ...EC T L N P O W E R S U P P L Y W I T H O V E R C U R R E N T P R O T E C T I O N D E V I C E WH JUNCTION BOX 1 T O 1 1 5 V A C 1 0 6 0 H Z ID BLOWER PRSEEURE SWITCH HEAT H GND WH RD WH GND BURNER COM...

Страница 37: ...37 2005 Goodman Company L P is a trademark of Maytag Corporation and is used under license to Goodman Company L P All rights reserved 1810 Wilson Parkway Fayetteville TN 37334 www amana hac com...