20
We reserve the right to modify technical specifications without prior notice.
83050800aUK – Translation of the operating manual
© Alpha-InnoTec GmbH
Commissioning
carry out a thorough installation check and work
through the items on the general checklist…
“General checklist”.
The installation check will prevent damage to the
heat pump system that can be caused by incorrectly
carried out work.
Ensure that…
•
the load power supply (compressor) has a
clockwise rotary field
.
•
the heat pump is
installed and assembled
according to the requirements in this operating
manual.
•
the electrical installation work has been carried
out properly.
•
a
3-pole
fuse has been installed for the
compressor. It must have a contact opening gap of
at least 3 mm. A
3 pole
miniature circuit breaker
must be installed.
•
the heating circuit and the heat source are flushed,
filled and bled thoroughly.
•
all valves and shut-off devices of the heating circuit
are open.
•
all valves and shut-off devices of the heat source
are open.
•
all pipe systems and components of the system
are leaktight.
carefully fill out and sign the completion report for
heat pump systems…
“completion report for heat pump systems”.
In Germany:
send completion report for heat pump systems
and general checklist to the manufacturer’s factory
customer service department.
outside of Germany:
send completion report for heat pump systems
and general checklist to the manufacturer’s local
partner.
“customer service” overview.
The heat pump system will be commissioned by
customer service personnel authorized by the
manufacturer. There is a fee for commissioning!
Domestic hot water tank
If the heat pump is to be used for domestic water heating,
you must integrate special domestic hot water tanks in
the heat pump system. choose a storage volume so that
the required quantity of domestic hot water is available
even during a power failure.
note:
The heat exchanger surface of the domestic hot
water tank must be dimensioned so that the
heating output of the heat pump is transferred
with minimum spread.
you can choose a domestic hot water tank from our
product range. They are optimally matched to your heat
pump.
note:
Integrate the domestic hot water tank in the
heat pump system as shown in the hydraulic
diagram for your system.
note:
A motor protection switch for the heat source
circulation pump is integrated in the heat pump!
An external motor protection switch must
be installed if a stronger groundwater pump is
required.
“Technical/scope of delivery” setting range