40
We reserve the right to make technical changes | 83055600dUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
SENSOR MEASURING RANGE
Type of sensor Measuring range
Autom. value in case of
sensor defect
PEX
-40°C to 40°C
-
TA
-50°C to 90°C
-5 °C
TBW
-45°C to 155°C
75 °C
TFB1
-20°C to 150°C
75 °C
TRL ext
-40°C to 40°C
5 °C
TVL
0°C to 100°C
5 °C
TVL2/TEH
0°C to 100°C
5 °C
TRL
0°C to 100°C
5 °C
Extension
board
TSS
-20°C to 140°C
150°C
TSK
-20°C to 140°C
150°C or 5°C
TB2
0°C to 100°C
75°C
TB3
0°C to 100°C
75°C
TEE
0°C to 100°C
5°C