System setting during commissioning
NOTE
The software automatically detects the connected heat pump type. Parameters that are not relevant for the system situation or
for the heat pump type are hidden from view. For this reason, some of the parameters contained in this overview may not ap-
pear in the display of your heating and heat pump controller.
Parameter
Factory setting
Adjustment during
commissioning *)
Value range (adjustable steps) Access
Program section “Cooling”
Outd. TP release
20 °C
°C
15 °C – 35 °C (
↕
1)
User
Outd. T-Dif1
5.0 K
K
1.0 K – 10 K (
↕
0.5)
User
set temperature MC1
20 °C
°C
18 °C – 25 °C (
↕
1
integration with “Sep.tank”:
5 °C – 25 °C (
↕
1)
User
hysteresis cool.contr
3.0 K
1 K – 5.0 K (
↕
0.5) Fitter
Target return cooling
20 °C
K
13 °C – 25 °C (
↕
0.5)
User
max. outs. temp.
12 h
h
0 h – 12 h (
↕
0.5)
User
min. outs. temp.
12 h
h
0 h – 12 h (
↕
0.5)
User
max. room. temp.
12 h
h
0 h – 12 h (
↕
0.5)
User
Temperatures
Limit Return
50 °C
°C
35 °C – 70 °C (
↕
1) Fitter
Hysteresis HC
2.0 K
K
0.5 K – 6.0 K (
↕
0.5) Fitter
hysteres.SW
2.0 K
K
1.0 K – 30.0 K (
↕
1) Fitter
RT incr.max
7.0 K
K
1.0 K – 10.0 K (
↕
1)
AS
Release 2 CP
5 °C
°C
-20 °C – 30 °C (
↕
1) Fitter
Release 2hg
-2 °C
°C
-20 °C – 20 °C (
↕
1) Fitter
Tp-defr.Air.
7 °C
°C
6 °C – 20 °C (
↕
1)
AS
TVth.disinf2
65 °C
°C
50 °C – 70 °C (
↕
1)
User
Flow 2. CP SW
50 °C
°C
10 °C – 70 °C (
↕
1) Fitter
T-outd. max
LWD: 35 °C
LWD-R: 40 °C
°C
20 °C – 45 °C (
↕
1)
AS
T-outd. min
-20 °C
°C
-20 °C – 10 °C (
↕
1) Fitter
T-HG max
130 °C
°C
100 °C – 150 °C (
↕
1)
Factory
T-def.airend
LWD: 2°C
LWD-R: 6 °C
°C
2 °C – 10 °C (
↕
1)
AS
lowering to
-20 °C
°C
-20 °C – 10 °C (
↕
1)
User
flow Max.
70 °C
°C
35 °C – 75 °C (
↕
1)
AS
Flow max. MC1
40 °C
°C
25 °C – 75 °C
User
min. AT flow max.
-7 °C
°C
-20 °C – 5 °C (
↕
1) Fitter
low limit of applic.
62 °C
°C
35 °C – 75 °C (
↕
1)
AS
hysteresis cool.contr
3.0 K
1 K – 5.0 K (
↕
0.5) Fitter
service water max
65 °C
°C
30 °C – 65 °C (
↕
0.5) Fitter
min.systemtemp.
15 °C
°C
15 °C – 30°C (
↕
0.5)
User
Defrost end temperature
45 °C
35 °C – 45 °C (
↕
1)
AS
minimal flow mc 1
20 °C
°C
20 °C – 40 °C (
↕
1) Fitter
maximum flow mc 1
45 °C
°C
25 °C – 75 °C (
↕
1) Fitter
Hysteresis 2.CP short
4.0 K
K
2 – 6 (
↕
1) Fitter
min. flow cooling
18 °C
°C
18°C – 25 °C (
↕
1) Fitter
min. flow cooling 2CP
10 °C
°C
7 °C – 20 °C (
↕
1) Fitter
*) Please enter the adjusted values. If 2 heat pumps are connected, enter both values. Mark not applicable with — .