No.

Display

Description

Remedy

724

Tempdiff defrosting

Please call fitter

Temperature spread in the heating circle is > 15 K during 

defrosting (=danger of frost).

Check function and location of the flow and 

return sensor, HCP capacity, overflows and 

heating circles. 

725

System error DHW

Please call fitter

Domestic hot water faulty, desired tank temperature is fallen 

below substantially.

Check circulating pump DHW, tank filling, 

shutoff move and 3-way valve. Ventilate hot 

water and SW. 

726

Sensor mixing circ 1

Please call fitter

Break or short-circuit in the mixing circle sensor.

Check mixing circle sensor, plug and 

connection line. 

727

Brine pressure

Please call fitter

Brine pressure pressostat has responded during the pre-rinsing 

time or during operation.

Check brine pressure and brine pressure  

pressostat. 

728

Sensor HS Off

Please call fitter

Break or short-circuit in the heat source sensor at the HS outlet. Check heat source sensor, plug and 

connection line. 

729

Rotating field error

Please call fitter

Compressor without power after switching on.

Check rotating field and compressor. 

730

Screed heating error

Please call fitter

The screed heating program could not reach an FL temperature 

level in the specified time interval. Screed heating program 

continues running.

The screed heating program could not 

reach an FL temperature level in the 

specified time interval. Screed heating 

program continues running.

731

Timeout TDI

The temperature required for thermal disinfection could not be 

reached within the set switching times.

732

Cooling fault

Please call fitter

The hot water temperature of 16 °C has been fallen short of 

several times.

Check mixer and heating circulation pump. 

733

Anode fault

Please call fitter

Fault input of the impressed current anode has responded.

Check connection line between anode and 

potentio stat. Fill SW tank. 

734

Anode fault

Please call fitter

Error 733 present for more than two weeks and domestic hot 

water is locked.

Acknowledge error in order to release 

domestic hot water preparation again. 

Rectify 733.

735

Error Ext. En

Please call fitter

Only possible with installed  expansion board: Break or short-

circuit in the sensor “External energy source”.

Check sensor “External energy source”, plug 

and connection line. 

736

Error solar collector

Please call fitter

Only possible with installed  expansion board: Break or short-

circuit in the “solar collector” sensor.

Check “solar tank” sensor, plug and 

connection line. 

737

Error solar tank

Please call fitter

Only possible with installed  expansion board: Break or short-

circuit in the “solar tank” sensor.

Check “solar tank” sensor, plug and 

connection line. 

738

Error mixing circle 2

Please call fitter

Only possible with installed  expansion board: Break or short-

circuit in the “mixing circle 2” sensor.

Check “mixing circle 2” sensor, plug and 

connection line. 

739

Error mixing circle 3

Please call fitter

Only possible with installed  expansion board: Break or short-

circuit in the “mixing circle 3” sensor.

Check “mixing circle 3” sensor, plug and 

connection line. 

750

Return sensor external

Please call fitter

Break or short-circuit in the external return sensor.

Check external return sensor, plug and 

connection line. 

751

Phase monitoring fault

Phase-sequence relay has responded.

Check rotary field and phase-sequence 

relay. 

752

Flow error

Phase-sequence relay or flow switch has responded.

see errors No. 751 and No. 717.

755

Lost connection to slave

Please call fitter

A slave has not responded for more than 5 minutes.

Check network connection, switch, and IP 

addresses. Perform HP search if necessary.

756

Lost connection to master

Please call fitter

A master has not responded for more than 5 minutes.

Check network connection, switch, and IP 

addresses. Perform HP search if necessary.

757

Low-pressure fault in W/W-

appliance

Low-pressure pressostat in the W/W-appliance has triggered 

either repeatedly or for more than 20 seconds.

If this malfunction occurs three times, the 

installation can only be cleared again by 

authorised service personnel!

758

Defrosting malfunction

Five times in a row, defrosting has either lasted longer than 10 

minutes or was terminated with a feed temperature of < 10 °C.

Check flow rate.

Check flow sensor.

759

TDI message

Unable to correctly carry out thermal disinfection 5 times in 

succession.

Check setting of second heat generator and 

safety temperature limiter.

760

Defrosting fault

Defrosting ended 5 times in succession by maximum time 

(strong wind impinges on evaporator) .

Protect the fan and evaporator from strong 

wind.

761

LIN timeout

LIN timeout.

Check cable/contact.

762

Sensor evaporator intake

Tü sensor error (evaporator intake).

Check sensor, replace if necessary.

Содержание Luxtronik Series

Страница 1: ...HMD 2 Controller part 2 Scope of delivery Montage Electrical connections Software update Commissioning Switching on for the first time Addressed heat pump Program area Cooling Program area Service App...

Страница 2: ...parts confiden tially The information contained herein is protected by copyright No part of this information may be reproduced transmitted cop ied stored in electronic data systems or translated into...

Страница 3: ...stallation 39 Outputs 39 Inputs 39 Connections 39 Interfaces 39 Protection class 39 Temperature sensor characteristic curve 39 Sensor measuring range 40 SYSTEM SETTING DURING COMMISSIONING 41 ABBREVIA...

Страница 4: ...on the control board are assigned by the terminal diagram of the hydraulic module In addi tion you will find the assignment on the switchbox cover Scope of delivery Heating and heat pump regulator co...

Страница 5: ...drill them into the fixing point Insert dowels and screw the housing of the external sensor to the wall NOTE Dowels and screws for fastening the external sensor are not included in the scope of suppl...

Страница 6: ...downgrades can be carried out via the USB in terface on the control unit of the heating and heat pump control ler 1 Expose the USB interface on the control unit Part 1 of the controller manual program...

Страница 7: ...enu item Reset Startup Parameters appears on the dis play instead of the Startup guide menu item Switching on Commissioning When switching on the controller voltage or after a restart of the heating a...

Страница 8: ...e continues with further input prompts which concern the settings of your system for example with Further queries will follow The startup guide leads you step by step through several selec tion option...

Страница 9: ...gs made during commissioning startup guide This al lows you to quickly and easily reset the system to the status it had at startup The data is stored on the circuit board of the control unit Follow th...

Страница 10: ...s Heizungs und W rmepumpenreglers wird zu n chst ein Kommunikationsfehler ausgegeben Example of a connection error displayed on the screen Beispiel eines im Bildschirm angezeigten Kommunika tionsfehle...

Страница 11: ...hat heat pump 2 is currently ad dressed in the system s Service area If you want to call up information for the heat pump currently dis played 1 or 2 in the system area Service or want to make set tin...

Страница 12: ...ling The Cooling function with automatic changeover between heating mode and cooling mode depending on requirements can be used with reversible LWD heat pumps and one mixing cir cuit In order to use t...

Страница 13: ...e only during the summer months or shut off the cooling during the heating period by means of a room thermostat Otherwise it is possible that depending on the location of the outdoor sensor the system...

Страница 14: ...TIVE COOLING NOTE The active cooling function can only be used if the system is utilised in accordance with the corresponding hydraulic diagram There is otherwise no guarantee that the active cooling...

Страница 15: ...perature Intake compressor Compressor intake temperature Intake vapor Evaporator intake temperature Comp Heater Compressor heating temperature Superheat Superheating temperature Targeted Superheat Sup...

Страница 16: ...pening EEV heating Electronic expansion valve heating EEV cooling Electronic expansion valve cooling Undercooling EEV Calculated under cooling at the electronic expansion valve THG Grenze Maximum hot...

Страница 17: ...hours domestic hot water Operation hours cool Operation hours Cooling NOTE The compressors are only energised alternately follow ing the impulses A variation in the operation hours of the compressors...

Страница 18: ...eating DHW Defrost El Sup bl Software version RBE Software version of the room control unit RBE Defrost demand Defrosting requirement in Last defrost Time of last defrost Query error memory NOTE If 2...

Страница 19: ...e mixing circuit 1 Targ service water Set point temperature domestic hot water preparation target value max Highest requirement setpoint from the Smart system UFH total HC Number of floor heating circ...

Страница 20: ...ntroller maunual program area Service sec tion Data logger Cur room temp HC Current room temperature of the worst room in the heating circuit Targ room temp HC Target temperature of the worst room in...

Страница 21: ...Set the first digit by turning the turn push button and confirm the entry by pressing the button Move to the respective next entry field and repeat the steps described above Finally move to and save t...

Страница 22: ...at pump is set at an outside temperature of 20 C For further details see point min AT flow max and the following diagrams VL AT 20 C min AT Flow max Flow max low limit of applic Hysteresis HR setting...

Страница 23: ...tr Hysteresis cooling circuit Standard value for reversible air water heat pumps 3 K service water max Maximum domestic hot water temperature A value which is set to limit the maximum set temperature...

Страница 24: ...paration energises but only if this has been released previously in the heating mode Defr cycle max Defrost cycle time maximum time between two defrost processes You can find the time to be set for th...

Страница 25: ...d on No Remote maintenance function switched off part 1 of the controller manual program area Service sec tion Remote maintenance Yes Setting only effective with an outdoor temperature 0 C Heating cir...

Страница 26: ...ssor stage cuts in If the difference between the return flow set and actual values is greater than the setting Hysteresis 2 CP short then the second compressor stage cuts in after this time NOTE A com...

Страница 27: ...eating and floor heating circulating pump suppl pump additional circulating pump DHW pump Domestic hot water circulation pump fan heats pump Fan well or brine circulation pump MC open 1 Mixer 1 OPEN M...

Страница 28: ...ring this scrolling Efficiency pump The menu is not shown in full here Heat distrib sys Heat distribution system radiator Radiator s floor heat Floor heating control heating Control of the heating cir...

Страница 29: ...water Position Tank Integrated in the heat generator heat pump or associated hydraulic component Integrated Integrated directly in or on the heating or hot water storage tank no ZWE 1 connected Outle...

Страница 30: ...s applies Heating The heat pump operates in the setpoint value range plus increase heating HR heating hysteresis in heating mode NOTE Higher increases in temperatures can lead to loss of comfort in Sm...

Страница 31: ...B C D E F 3 AIT ait deutschland GmbH L1 L1 L1 L 2 2 IN1 IN2 IN3 A1 A2 A1 A2 IN4 IN5 A3 A1 nderung Datum Datum Bearbeiter Gepr ft Norm Name 09 10 2015 Pfleger R LWD LWD R SELECTING LANGUAGE OF THE SCRE...

Страница 32: ...the current tem perature setpoint of the screed heating program at the respective flow sensor by opening or closing the mixing circuit valve The mixing circuit control and temperatures have no influen...

Страница 33: ...sary for the screed heating phase to integrate additional heat gen erators in the system The menu is not shown in full here scroll down the screen Answer the confirmation prompt NOTE If you respond to...

Страница 34: ...se is switched off this must be set in the menu Mode of operation Deselect program area not required The example shown reveals that the menus of the pro gram area Heating are displayed in the screen T...

Страница 35: ...l temperature sensor plug and connection line 712 Domestic hot water sensor Please call fitter Break or short circuit in the domestic hot water sensor No fault shutdown Check domestic hot water sensor...

Страница 36: ...nsor External energy source Check sensor External energy source plug and connection line 736 Error solar collector Please call fitter Only possible with installed expansion board Break or short circui...

Страница 37: ...781 Liquid temp sensor before EXV Liquid temperature sensor upstream of the ex valve is defective Check the sensor connector and connection cable 782 Suction gas EVI temp sensor Suction gas EVI temper...

Страница 38: ...operation after 2 hours If the shutdown occurs 5 times within 24 hours error 800 is written to the fault memory Remove energy from desuperheater memory The machine can be restarted as soon as the temp...

Страница 39: ...quickly Technical Data INSTALLATION Only in frost free dry and weatherproof rooms Ambient temperature 0 C 35 C Electrical connection 230 V AC 18 VA 0 1 A max power consumption regulator without any a...

Страница 40: ...sor Measuring range Autom value in case of sensor defect PEX 40 C to 40 C TA 50 C to 90 C 5 C TBW 45 C to 155 C 75 C TFB1 20 C to 150 C 75 C TRL ext 40 C to 40 C 5 C TVL 0 C to 100 C 5 C TVL2 TEH 0 C...

Страница 41: ...turn 50 C C 35 C 70 C 1 Fitter Hysteresis HC 2 0 K K 0 5 K 6 0 K 0 5 Fitter hysteres SW 2 0 K K 1 0 K 30 0 K 1 Fitter RT incr max 7 0 K K 1 0 K 10 0 K 1 AS Release 2 CP 5 C C 20 C 30 C 1 Fitter Releas...

Страница 42: ...ixed Tp Analog In Fitter setting mc1 Set AT Set AT Fixed Tp Fitter Cooling Fixed Tp Set AT Fixed Tp User screed heating w mixer wo mixer w mixer User El Anode device dependent No Yes AS Heating limit...

Страница 43: ...SW Heating Fitter Position Integrated Integrated Tank Fitter Outlet installation dependent output contact Fitter Second heat gen 2 Type No No El Rod Fitter Function No No Heating SW Fitter Position T...

Страница 44: ...LWAV Performance controlled Air Water heat pump outdoor LWC Air Water Compact heat pump LWCV Performance controlled Air Water Compact heat pump LWD Air Water heat pump Dual Abbreviation Meaning LWDV...

Страница 45: ...estic hot water UFH Floor heating circuit UWP Circulation pump VBO Fan well or brine circulation pump VD Compressor W W Water water heat pump WP Heat pump WW Domestic hot water WWC Water water Compact...

Страница 46: ...46 We reserve the right to make technical changes 83055600dUK Translation of the original instruction manual HMD 2 ait deutschland GmbH...

Страница 47: ...47 We reserve the right to make technical changes 83055600dUK Translation of the original instruction manual HMD 2 ait deutschland GmbH...

Страница 48: ...ait deutschland GmbH Industriestra e 3 D 95359 Kasendorf E info alpha innotec de W www alpha innotec de alpha innotec an ait deutschland GmbH brand UK...

Отзывы: