Chapter 4
Programming
Input 1
Programs the desired operation of the Control Module to a change in status of Input #1 wired to
control terminal #11 (24V DC).
Disable, Start, Coast, Stop Option, Start/
Coast, Start/Stop, Dual Ramp, OL
Select, Fault, Fault NC, Clear Fault,
Emerg Run
Start/Coast
Input 2
Programs the desired operation of the Control Module to a change in status of Input #2 wired to
control terminal #10 (24V DC).
Disable
Aux 1 Config
Aux 1 Config Programs the control function of the Auxiliary Output Contact #1, wired across control
terminal #4 and #5.
(4)
Normal, UTS, Fault, Alarm, Ext Bypass,
Ext Brake, Aux Control
(7)
, Network 1,
Network 2, Network 3, Network 4,
Fan Control
Normal
Aux 2 Config
Programs the control function of the Auxiliary Output Contact #2, wired across control terminal #6
and #7.
(4)
Overload Class
Required for motor protection. Lets you select the time-to-trip for the built-in Motor Overload.
This selection is based on the type of motor being used and the application it is being applied to.
5…30
10
Service Factor
Required for motor protection. This value is taken directly from the nameplate and used by the
controller to determine the ultimate Overload Trip Current.
0.01...1.99
1.15
Motor FLC
Required for motor protection. This programmed value is taken directly from the motor
nameplate.
1.0...2200.0 A
1.0 A
Starting Torque NOT used for a Soft Start.
0...300% RMT
100% RMT
Max Torque
NOT used for a Soft Start.
0...300% RMT
250% RMT
Rated Torque
NOT used for a Soft Start.
0...100,000 N•m
10 N•m
Rated Speed
NOT used for a Soft Start.
750, 900, 1000, 1200, 1500, 1800,
3500, 3600 rpm
1800 rpm
(1) In the AUTO Detect [default] selection, the controller automatically checks the motor configuration.
(2) Enter a value to limit the current but not low enough to inhibit the start cycle.
(3) The stopping mode does not need to match the starting mode (for example, a Soft Start can have a stop mode programmed for [Coast], or Linear Stop—there is no Current Limit Stop or Torque Stop
mode).
(4) Relay Operational Options (for example, ON and OFF delay, etc.) are provided in the File: Setup, Group: I/O selection sequence. See
Table 11
.
(5) Kickstart is available when using Soft Start. A Kickstart Level and Time must be configured if this mode is used. Access these parameters via the Starting Setup Group. The Starting Setup Group can be
accessed with the HIM from the Port <00> DEV PARAM folder under the File-Group, File: Setup, Group: Starting selection sequence (see
Table 11
). Setting either parameter to zero disables Kickstart.
(6) You can also program a start delay time to delay starting for a period of time after the initiation of the START command. The Start Delay parameter can be accessed from the Group Starting selection
as noted.
(7) Any auxiliary output configured for Aux Control using the AuxX Config parameter is under control of its associated bit from the Aux Control, Parameter 180. See Parameter 180 information for bit
assignments.
NOTE: This function enables forcing an output, ON or OFF.
Table 12 - Soft Start Parameter Group (Continued)
Parameter
Name
Description
Options
Default
Value
ATTENTION:
For Overload Protection, it is critical that you enter the data into
the SMC-50 control module as it appears on the motor nameplate.
Содержание SMC-50
Страница 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Страница 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Страница 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Страница 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Страница 134: ...134 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 6 Optional HIM Operation Notes ...
Страница 144: ...144 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 7 Communications Notes ...
Страница 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Страница 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Страница 240: ...240 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix A Parameter Information Notes ...
Страница 242: ...242 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix B Controller Duty Cycle Ratings Notes ...
Страница 250: ...250 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix C 1560F and 1562F Relay Control Notes ...
Страница 280: ...280 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix G Using DeviceLogix Notes ...
Страница 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Страница 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Страница 291: ......