152
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Chapter 8
Diagnostics
Open Bypass
A
11
N
N
N
A
F
Open Bypass Phase A
Device senses that the bypass contactor
did not close on the respective phase.
B
12
N
N
N
A
F
Open Bypass Phase B
C
13
N
N
N
A
F
Open Bypass Phase C
No Load
14
N
Y
Y
F/A
The SMC-50 control module can determine if a load connection
exists (total load lost or all load leads lost) and a No Load Fault and/or
Alarm can be indicated.
Open Load
A
15
N
Y
Y
F/A
An Open Load A
Fault/Alarm indicates that the Phase X
load lead connection is OFF/Open.
B
16
F/A
An Open Load B
C
17
F/A
An Open Load C
Voltage
Unbalance
18
Y
Y
Y
F/A
Indicates that when the calculated unbalance level is greater than
the user-defined Fault and/or Alarm level. See Chapter 4 for calculated
value details.
Overvoltage
19
Y
Y
Y
F/A
Indicates that if the average line voltage is greater than the user-
defined Fault and/or Alarm level.
Undervoltage
20
Y
Y
Y
F/A
Indicates that if the average line voltage is less than the user-
defined Fault and/or Alarm level.
Overload
21
Y
(1)
Y
Y
F/A
Enabled in the Motor Protection Group by programming the:
Overload Class, Overload Reset, Motor FLC, and Service Factor.
Underload
22
Y
Y
Y
F/A
Motor operation will halt (Fault only) if the value of the motor’s
average RMS current is less than the user-defined value.
Jam
23
Y
Y
Y
F/A
Indicates that the motor current increases above the user-defined
Fault and or Alarm level while the motor is running at speed. This F/A
condition is not active during starting or stopping.
Stall
24
Y
Y
Y
F/A
Condition exists and a Fault/Alarm is generated if the SMC-50
control module senses that the motor is NOT Up-to-Speed (UTS) at the
end of the programmed starting ramp time plus the time programmed
in the Stall Delay time.
Phase Reversal
25
N
Y
Y
F/A
Fault/Alarm is indicated when the incoming power to the SMC-50
control module is in any sequence other than ABC.
Exp Removed
26
N
N
N
A
F
Removing an expansion module (device) (for example, a 150-SM4)
from a SMC-50 control module will result in a x026 fault, where "x" is
the SMC-50 control module port number (7, 8, or 9) the expansion
module was installed. DPI devices (for example, 20-HIM-A6 or 20-
COMM-X) will only generate this fault if its associated bit in Logix Mask
parameter is set.
NOTE:
If an expansion module (device) (for example, a 150-SM4 is
removed from a SMC-50 controller), the message "Device Conflicts Port
xy Not Found" is displayed on the HIM or PC software) when power
returns.
Exp Incompat
27
N
N
N
A
F
Inserting an expansion module or DPI device into an incompatible
control module port number or inserting an expansion module into a
control module with incompatible version of firmware results in this
Fault. The port number of the offending device is included as the first
digit of this Fault code.
Expansion
28
N
N
N
A
F
General Fault that can be generated by an expansion or peripheral
device. The port number of the offending device is included as the first
digit of this Fault code.
Table 57 - Linear Listing—Fault and Alarm Code Overview (Continued)
Fault/Alarm
Code Name
F/A
Co
de
Time
Del
ay A
vail
.
F/A
Bit
Ena
ble
Restar
t Enable
Description
F/A= Fault and Alarm, A= Alarm, F= Fault
Содержание SMC-50
Страница 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Страница 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Страница 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Страница 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Страница 134: ...134 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 6 Optional HIM Operation Notes ...
Страница 144: ...144 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 7 Communications Notes ...
Страница 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Страница 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Страница 240: ...240 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix A Parameter Information Notes ...
Страница 242: ...242 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix B Controller Duty Cycle Ratings Notes ...
Страница 250: ...250 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix C 1560F and 1562F Relay Control Notes ...
Страница 280: ...280 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix G Using DeviceLogix Notes ...
Страница 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Страница 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Страница 291: ......