Chapter 4
Programming
Set up Start Profile 2 by using the Dual Ramp parameter set. You can use the
HIM to access Dual Ramp from the <Port 00> DEV PARAM folder (see
Table 11 on page 96
). Use the parameters in
Table 18
to program a Dual Ramp
adjustment.
Motor Protection
The Motor Protection Group (see
Table 21 on page 110
) is used to program
motor and starter protection functions. The Motor Protection Group is accessed
from the HIM using the Port 00 DEV PARAM folder under the File-Group,
File: Motor Protection selection sequence. By using this file group, the SMC-50
control module lets you individually enable, disable, or restart the motor and
starter Faults and Alarms. Each of the 21 different Motor/Starter Protection
Setup groups (for example, Overload, Underload, Jam, Stall, Voltage Unbal, etc.)
has at least one selection for Fault Enable, Alarm Enable, and Restart Enable.
.
Table 18 - Dual Ramp Start with Stop Parameters
Parameter Name
Description
Options
Default Value
Starting Mode 2
Select the desired starting mode for Profile 2
Soft Start, Full Voltage, Linear
Speed, Torque Start, Current
Limit, Pump Start.
(3)(4)
—
Ramp Time 2
Programs the Profile 2 time period that the controller will ramp the output voltage to
full voltage and motor speed from the programmed Initial Torque value.
0…1000 s
10 s
Current Limit Level 2
The Profile 2 setting limits the current supplied in the motor throughout the Soft
Start, Linear Speed, or Torque Ramp cycle.
(1)
50...600% FLC
350% FLC
Initial Torque 2
Initial Torque 2 The initial reduced output voltage (torque) level for the Profile 2
Voltage Ramp to the motor is established and adjusted with this parameter. The
torque level at which the ramp begins for Profile 2. NOTE: Not used for Torque Ramp.
0…90% LRT
70% LRT
Starting Torque 2
Starting Torque 2 For a Torque Ramp Start, the programmed initial or start torque
point for Profile 2. This parameter is not used for other starting modes.
0…300% RMT
100% RMT
Max Torque 2
For Start Profile 2, the programmed torque end point for a Torque Ramp start. This
parameter is not used for other starting modes.
0…300% RMT
250% RMT
Kickstart Time 2
For Start Profile 2, if required, a boost of current (torque) is provided to motor for this
programmed time period.
(2)
0…2 s
0 s
Kickstart Level 2
For Start Profile 2, if required, this parameter programs the amount of current (torque)
applied to the motor during Kickstart time.
(2)
750, 900, 1000, 1200, 1500,
1800, 3500, 3600 rpm
1800 rpm
(1) Enter a value to limit the current but not low enough to inhibit the start cycle.
(2) Available for Soft Start, Current Limit, and Torque Start modes. Set to zero to disable Kickstart.
(3) Torque Ramp and Linear Speed Starting modes require you to perform a Motor Tuning Cycle. The SMC-50 control module does this automatically the first time the motor is run. You can also force this
manually by setting the Force Tuning, Parameter 194, to TRUE (=1), which is accessed from the File Setup, Group Adv. Tuning or by pressing and holding the SMC-50 controller’s Reset button for 10
seconds with the motor stopped.
(4) You can also program a start delay time and will apply to both Start Profile 1 and Start Profile 2. The Start Delay parameter can be accessed from the Group Starting selection (see
Table 11
).
IMPORTANT
The majority of parameters have a Fault and an Alarm setting.
Содержание SMC-50
Страница 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Страница 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Страница 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Страница 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Страница 134: ...134 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 6 Optional HIM Operation Notes ...
Страница 144: ...144 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 7 Communications Notes ...
Страница 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Страница 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Страница 240: ...240 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix A Parameter Information Notes ...
Страница 242: ...242 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix B Controller Duty Cycle Ratings Notes ...
Страница 250: ...250 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix C 1560F and 1562F Relay Control Notes ...
Страница 280: ...280 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix G Using DeviceLogix Notes ...
Страница 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Страница 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Страница 291: ......