Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
137
Communications
Chapter 7
Control Enable
Logic Mask, Parameter 148, lets you configure whether a communication device
(HIM or network connection) can perform motor control commands such as
starting. Each communication port (1 through 4) can be enabled (bit= 1) or
disabled (bit = 0) as required. When a given device is enabled through the logic
mask that device is allowed to execute control commands. In addition,
disconnecting any device with the logic mask enabled will result in an Exp
Removed (X026)
(1)
communication fault. You can disconnect adevice that is
disabled through the logic mask without causing a fault
(2)
Logic Mask Enable/Disable using a HIM
To enable motor control using a connected HIM, follow the procedure below
with the connected HIM’s programming keys.
The Bulletin 20-HIM-A6 provides start and stop control of the controller.
However, the Logic Mask factory default settings disable control commands
other than Stop through the controller’s DPI ports 1, 2, 3, or 4.
To enable motor control from either of the four ports using a connected 20-
HIM-A6, the following steps must be performed from the SMC-50 control
module standard power-up screen.
1.
Press the
key. Use the right or left arrow key on the keypad to
display the <00> DEV PARAM folder screen.
2.
Select/highlight the File-Group.
3.
Press the
(enter) key. The Port 00 Param File-Group screen
appears.
4.
Press the
to select FILE Communications, then press
. The
GROUP Comm Masks and Data Links screen appears.
(1) When a given device is disabled through the logic mask that device cannot execute control commands, but can still be used for
configuration and monitoring. X = DPI port number of the device causing the Fault.
(2) If a 20-HIM-A6 is enabled for control via the Logic Mask, it can still be removed using the HIM control screen. See
IMPORTANT
Stop commands override all start commands and can be initiated from the
hardwired inputs or any DPI port regardless of the logic mask.
TIP
Ensure the Advanced Access Level is selected, located at the bottom of the
DEV PARAM screen. For additional configuration details, see
Access Level Modification Using the HIM on page 86
5
5
Содержание SMC-50
Страница 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Страница 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Страница 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Страница 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Страница 134: ...134 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 6 Optional HIM Operation Notes ...
Страница 144: ...144 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 7 Communications Notes ...
Страница 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Страница 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Страница 240: ...240 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix A Parameter Information Notes ...
Страница 242: ...242 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix B Controller Duty Cycle Ratings Notes ...
Страница 250: ...250 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix C 1560F and 1562F Relay Control Notes ...
Страница 280: ...280 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix G Using DeviceLogix Notes ...
Страница 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Страница 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Страница 291: ......