Parameter Information
Appendix A
256
Lag PF Ov F Lvl
-1/0
0.00
Allows the user to enter a value for the Lagging Power Factor
Over Fault Level (Lag PF Ov F Lvl). If the current actual Power
Factor value lags more than the Lag PF Ov F Lvl for a time period
greater than that defined by Lag PF Ov F Dly, a Lag PF Ov Fault
will be signaled.
R/W
257
Lag PF Ov F Dly
Secs
0.1/99
0.1
Allows the user to enter a time value for the Lagging Power
Factor Over Fault Delay (Lag PF Ov F Dly). If the current actual
Power Factor value lags more than the Lag PF Ov F Lvl for a time
period greater than that defined by Lag PF Ov F Dly, a Lag PF Ov
Fault will be signaled.
R/W
258
Lag PF Ov A Lvl
-1/0
0.00
Allows the user to enter a value for the Lagging Power Factor
Over Alarm Level (Lag PF Ov A Lvl). If the current actual Power
Factor value lags more than the Lag PF Ov A Lvl for a time period
greater than that defined by Lag PF Ov A Dly, a Lag PF Ov Alarm
will be signaled.
R/W
259
Lag PF Ov A Dly
Secs
0.1/99
0.1
Allows the user to enter a time value for the Lagging Power
Factor Over Alarm Delay (Lag PF Ov A Dly). If the current actual
Power Factor value lags more than the Lag PF Ov A Lvl for a time
period greater than that defined by Lag PF Ov A Dly, a Lag PF Ov
Alarm will be signaled.
R/W
260
Lag PF Un F Lvl
-1/0
0.00
Allows the user to enter a value for the Lagging Power Factor
Under Fault Level (Lag PF Un F Lvl). If the current actual Power
Factor value lags less than the Lag PF Un F Lvl for a time period
greater than that defined by Lag PF Un F Dly, a Lag PF Un Fault
will be signaled.
R/W
261
Lag PF Un F Dly
Secs
0.1/99
0.1
Allows the user to enter a time value for the Lagging Power
Factor Under Fault Delay (Lag PF Un F Dly). If the current actual
Power Factor value lags less than the Lag PF Un F Lvl for a time
period greater than that defined by Lag PF Un F Dly, a Lag PF Un
Fault will be signaled.
R/W
262
Lag PF Un A Lvl
-1/0
0.00
Allows the user to enter a value for the Lagging Power Factor
Under Alarm Level (Lag PF Un A Lvl). If the current actual Power
Factor value lags less than the Lag PF Un A Lvl for a time period
greater than that defined by Lag PF Un A Dly, a Lag PF Un Alarm
will be signaled.
R/W
263
Lag PF Un A Dly
Secs
0.1/99
0.1
Allows the user to enter a time value for the Lagging Power
Factor Under Alarm Delay (Lag PF Un A Dly). If the current
actual Power Factor value lags less than the Lag PF Un A Lvl for a
period greater than that defined by Lag PF Un A Dly, a Lag PF Un
alarm will be signalled.
R/W
264
Motor Restart En
(Refer to 264)
Manual P111:
The SMC-50 can be configured to automatically reset the
overload fault when it has cooled to the set Overload Reset
Level, Parameter 80. The Motor Restart Enabled (Motor Restart
En), Parameter 264, must be enabled (Overload = Set) to allow
the Overload Reset Level parameter to function.
Table 66 - SMC -50 Parameter List (Continued)
Number
Name
Unit
Min/Max
Default
Enum Text
Description
R/W
Содержание SMC-50
Страница 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Страница 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Страница 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Страница 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Страница 134: ...134 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 6 Optional HIM Operation Notes ...
Страница 144: ...144 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 7 Communications Notes ...
Страница 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Страница 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Страница 240: ...240 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix A Parameter Information Notes ...
Страница 242: ...242 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix B Controller Duty Cycle Ratings Notes ...
Страница 250: ...250 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix C 1560F and 1562F Relay Control Notes ...
Страница 280: ...280 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix G Using DeviceLogix Notes ...
Страница 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Страница 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Страница 291: ......