82
Rockwell Automation Publication 1500-UM055I-EN-P - December 2021
Appendix A ArcShield Unit Information
Each ArcShield line-up includes a chimney exhaust section that extends
vertically directly above the enclosure.
Chimney Exhaust Considerations
1. From the outlet of the chimney, there needs to be a minimum distance of
1.7 m (67 in.) from the top of the chimney to the ceiling, and 1 m (39 in.) on
each side.
2. No obstructions (eg. piping) can be in the path of the exhaust within this
2 m (78 in.) height requirement.
Plan the location where the chimney will exhaust. Ensure that:
•
There is no access to personnel while equipment is energized.
•
Area is free of flammable material or vapors.
•
Ensure that adequate space is provided around the chimney exhaust as
outlined in
.