Chapter 1 Installation – Standard Enclosure
Figure 9 - Side Bus Access Cover Removed
Front Access– Access to Power Bus
1. Open the doors and remove the hinge pins.
2. Open the low voltage cell doors (refer to
3. Disconnect the control wiring harness from the wire plug at the lower
left side of the contactor.
4. Remove the two 1/4-20 self-tapping screws from the center vertical
channel (see
).
5. Pull on the center vertical channel to swing out the low voltage panel.
ATTENTION:
To avoid shock hazards, lock out incoming power (see
Power Lock-out Procedure on page 53
) before working on the
equipment. Verify with a hot stick or appropriate voltage measuring
device that all circuits are voltage free. Failure to do so may result in
severe burns, injury or death.