Rockwell Automation Publication 1500-UM055I-EN-P - December 2021
Chapter 4 Maintenance
Fuse Removal and
Replacement
Figure 51 - Medium Voltage Power Fuses
ATTENTION:
Only personnel who have been trained and understand the
Bulletin 1500 product line are to work on this equipment. Suitable safety
equipment and procedures are to be used at all times.
Bolt-on Fuses
Clip-on Fuse
Clip-on Fuse Extractor
ATTENTION:
Servicing energized industrial control equipment can be
hazardous. Severe injury or death can result from electrical shock,
burn, or unintended actuation of control equipment. Hazardous
voltages may exist in the cabinet even with the circuit breaker in the
OFF position. Recommended practice is to disconnect or lock out
control equipment from power sources, and confirm discharge of
stored energy in capacitors. If it is necessary to work in the vicinity of
energized equipment, the safety related work practices of NFPA 70E,
Electrical Safety requirements for Employee Work places, must be
followed.
ATTENTION:
To prevent electrical shock, ensure the main power has
been disconnected and equipment has been tagged and locked out.
Verify that all circuits are voltage free using a hot stick or appropriate
voltage-measuring device. Failure to do so may result in injury or death.
The main power fuse has a pop up indicator pin located at one end
of the fuse. When a fuse has opened, the indicator will be in its
extended position. The fuse should be oriented in the fuse clip
assembly so that the indicator is at the top.
Содержание 1512B
Страница 6: ...6 Rockwell Automation Publication 1500 UM055I EN P December 2021 Notes...
Страница 74: ...74 Rockwell Automation Publication 1500 UM055I EN P December 2021 Chapter 4 Maintenance Notes...
Страница 76: ...76 Rockwell Automation Publication 1500 UM055I EN P December 2021 Chapter 5 Spare Parts Notes...
Страница 106: ...106 Rockwell Automation Publication 1500 UM055I EN P December 2021 Appendix E History of Changes Notes...