
Rockwell Automation Publication 1407-UM001H-EN-P - November 2014
!PPENDIX%
Detailed CGCM Unit Tag Descriptions
•
kW_LS_OutV
– This tag sets the voltage that the CGCM unit attempts
to output from the load-sharing terminals.
•
kVAR_LS_OutV
– This tag is reserved for future use.
•
LS_FS_V
- This tag sets the voltage the load share output reaches when
the generator is producing 1 p.u. kVA. The base for this calculation is the
calculated generator kVA.
•
LSRate
- This tag configures the time required for the load share output to
change the per unit amount defined above.
•
LSLimit
- This tag configures the amount of per unit change allowed in
the load share output per unit of time defined below.
•
KWAnalogTargetPUValue
– The value of this tag is used to provide the
bias to the load share lines when the kW_LS_BridgeEN tag is set to 1.
•
KWDigitalTargetPUValue
– This tag is reserved for future use.
•
KVARAnalogTargetPUValue
– This tag is reserved for future use.
•
KVARDigitalTargetPUValue
– This tag is reserved for future use.
,OAD3HARING/UTPUTSFROMTHE#'#-5NIT
•
kVAR_LS_Active
– This tag is reserved for future use.
•
kW_LS_Active
- This tag follows the kW_LS_En tag setting in the
Scheduled Write tag.
•
LS_Err
– This tag reports the load share error that is the difference
between the kW_LS_OutV and the kW_LS InputV.
•
kW_LS_InputV
– This tag reports the voltage present at the load-sharing
terminals.
•
kW_PU_Load
- This tag reports the total p.u. kVA being produced by the
active phases of the generator. The base for this calculation is the
configured generator kVA.
•
kW_AnalogPU_Load
– This tag reports the value of the voltage present
at the load share terminals divided by the configured full scale voltage. It
represents the system per unit load.
•
kVAR_LS_InputV
-
The product of the RMS magnitude of the reactive
portion of the differential current flowing in the input CT and the
generator terminal voltage is computed. The product is divided by the
rated kVA to determine the reported value for this tag.
•
kVAR_PU_Load
- This tag reports the total p.u. kVAR being produced by
the active phases of the generator. The base for this calculation is the
configured generator kVA.
•
kVAR_AnalogPU_Load
– This tag reports the difference between the
KVAR_PU_Load and the kVAR_LS_inputV.
Содержание 1407-CGCM
Страница 1: ...Combination Generator Control Module Catalog Numbers 1407 CGCM User Manual...
Страница 4: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 3UMMARY OF HANGES OTES...
Страница 8: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 0REFACE OTES...
Страница 12: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER General Information OTES...
Страница 14: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Installation IGURE 5NIT VERALL IMENSIONS...
Страница 70: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Operation OTES...
Страница 106: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Configuration OTES...
Страница 126: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Startup OTES...
Страница 152: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER CGCM Unit Software Interface OTES...
Страница 168: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 HAPTER Troubleshooting OTES...
Страница 196: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX CGCM Unit Math Models OTES...
Страница 212: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 PPENDIX Specifications OTES...
Страница 250: ...Rockwell Automation Publication 1407 UM001H EN P November 2014 NDEX OTES...
Страница 251: ......